Replacing the Measuring System<br />
12 Replacing the Measuring System<br />
The following points must be noted when replacing the measuring system:<br />
●<br />
●<br />
●<br />
●<br />
●<br />
●<br />
●<br />
The new measuring system must have the same article number as the measuring<br />
system being replaced; any deviations must be expressly clarified with<br />
<strong>TR</strong>-<strong>Electronic</strong>.<br />
It must be ensured that the PROFIBUS address set via hardware switch for the<br />
new measuring system matches the previous PROFIBUS address.<br />
If a bus termination was provided for the measuring system being replaced, this<br />
must also be provided for the new measuring system.<br />
The new measuring system must be installed in accordance with the<br />
specifications and requirements in chapter "Assembly" on page 126.<br />
The new measuring system must be connected in accordance with the<br />
specifications in chapter "Connection" on page 134.<br />
As the F-Parameters and iParameters of the measuring system are stored in the<br />
safety program of the control, the new measuring system is parameterized with<br />
the projected settings in the start-up phase.<br />
When recommissioning the replaced measuring system, correct functioning must<br />
be ensured first of all by means of a protected test run.<br />