PROFIBUS / PROFIsafe - Commissioning<br />

6.6.2.2.4 Safe-Control<br />

Unsigned8<br />

Byte X+8<br />

Bit 7 – 0<br />

Data 2 7 – 2 0<br />

Bit<br />

Description<br />

iPar_EN: iParameter assignment unlocked<br />

2 0 The bit must be set indirectly via a variable of the F-Host in order to be<br />

able to execute the preset adjustment function, see chapter "Preset<br />

Adjustment Function" on page 189.<br />

OA_Req: Operator acknowledgement required<br />

The bit is set by the F-Host driver after detection and elimination of an<br />

error in the safety-oriented communication. The bit is also set if the<br />

measuring system/F-Host could not be synchronously integrated into the<br />

bus operation at start-up of the F-System.<br />

2 1 An operator acknowledgement is displayed via the green LED (3x with<br />

5 Hz) in relation to the measuring system. In this case a reintegration of<br />

the function blocks contained in the safety program must be performed.<br />

In this way the counters contained in the F-Host and F-Device for the<br />

virtual consecutive numbers are synchronized. The measuring system is<br />

then reset from safe status, output of passivated data, to normal status,<br />

output of cyclical data.<br />

R_cons_nr: Resetting of the counter for the virtual consecutive no.<br />

2 2 The bit is set when the F-Host detects an F-Communication error, either<br />

via the status byte or itself.<br />

2 3 reserved<br />

activate_FV: Activate fail-safe values<br />

The bit is set inside the device via the firmware if the measuring system<br />

2 4 can no longer output fail-safe data due to a device error, errors in the<br />

safety-oriented communication or at start-up of the F-System. The<br />

measuring system outputs its passivated data instead.<br />

Toggle_h: Toggle bit<br />

The toggle bit is host-based and causes the incrementation of the virtual<br />

2 5 consecutive numbers in the F-Device. The toggle bit is used to<br />

synchronize the counters in the measuring system/F-Host for generation<br />

of the virtual consecutive number.<br />

2 6 -2 7 reserved<br />

The Safe-Control register can only be indirectly accessed from a F-Runtime Group<br />

via the safety program with the aid of variables of the F-Periphery-DB, see chapter<br />

"Access to the safety-oriented data channel" on page 183.<br />

Printed in the Federal Republic of Germany<br />

© <strong>TR</strong>-<strong>Electronic</strong> GmbH 2010, All Rights Reserved<br />

05/25/2011 <strong>TR</strong> - ECE - BA - DGB - 0079 - 03 Page 151 of 207