Troubleshooting and Diagnosis Options<br />
11.2.1.4 Master address<br />
Standard diagnosis byte 4<br />
The slave enters the station address of the master into this byte, after the master has<br />
sent a valid parameterization telegram. To ensure correct function on the PROFIBUS<br />
it is imperative that, in the case of simultaneous access of several masters, their<br />
configuration and parameterization information exactly matches.<br />
11.2.1.5 Manufacturer's identifier<br />
Standard diagnosis byte 5 + 6<br />
The slave enters the manufacturer's ID number into the bytes. This is unique for each<br />
device type and is reserved and stored by the PNO. The ID number of the measuring<br />
system is 0x0CE3.<br />
11.2.1.6 Length (in bytes) of the extended diagnosis<br />
Standard diagnosis byte 7<br />
If additional diagnosis information is available, the slave enters the number of bytes<br />
(including this one) at this point, which still follows in addition to the standard<br />
diagnosis.<br />
11.2.2 Extended diagnosis<br />
In addition to the DP standard diagnosis report the measuring system provides an<br />
extended diagnosis report which contains the module status:<br />
Status block<br />
Byte 7 Byte 8 Byte 9 Byte 10 Byte 11<br />
Header Status type Slot no. Status-ID Module status<br />
0x09 0x82 0x__ 0x00 0x00 or 0x03<br />
●<br />
●<br />
●<br />
●<br />
●<br />
Header:<br />
– Number of bytes in addition to standard diagnosis, including Byte 7<br />
Status type:<br />
– Status block with module status<br />
Slot no.:<br />
– Specification of slot no., which is defective<br />
Status-ID:<br />
– No further differentiation<br />
Module status:<br />
– 0x00 = valid data from this module<br />
– 0x03 = invalid data, missing module<br />
Is reported by the measuring system if a CRC error is present in the<br />
F-Parameters or iParameters<br />
Bytes 12 to 15 are intended for service purposes<br />
Printed in the Federal Republic of Germany<br />
© <strong>TR</strong>-<strong>Electronic</strong> GmbH 2010, All Rights Reserved<br />
05/25/2011 <strong>TR</strong> - ECE - BA - DGB - 0079 - 03 Page 195 of 207