SYNCHROPHASORS - INITIATIVE IN INDIA JUNE 20125.1.3 Case Study-8: Multiphase fault at Khedar TPS on 5-Apr-2012Figure 51 shows 400kV Hisar bus voltage profile dur<strong>in</strong>g the occurrence of a multiphase fault atKhedar TPS <strong>in</strong> Northern region. It can be observed that the 1 st fault <strong>in</strong> B-phase got cleared <strong>in</strong>around 200ms. A second fault <strong>in</strong>volv<strong>in</strong>g R & Y phase occurs 680milli second after occurrence of1 st fault. The second fault gets cleared <strong>in</strong> 120 milli seconds.Figure 51: Voltage profile corroborat<strong>in</strong>g the fault clearance time at HissarPOSOCO Page 64 of 143