SYNCHROPHASORS - INITIATIVE IN INDIA JUNE 20125.3 Detection of exceptional grid events<strong>Synchrophasor</strong> data has also been utilized to detect load throw off or generation loss <strong>in</strong> the gridas described ahead.5.3.1 Case Study-16: Partial disturbance due to voltage collapseA partial disturbance caused by voltage collapse occurred <strong>in</strong> 220 kV Punjab system on 20th July2011. The voltage at 220 kV Bhat<strong>in</strong>da and 220 kV Lehra Mohabbat was reported to have goneas low as 78 kV and 92kV respectively. The voltage profile of 400 kV Moga bus dur<strong>in</strong>g the eventis shown <strong>in</strong> the below figure 59. It can be observed that there is around 4kV to 6kV dip <strong>in</strong>voltages <strong>in</strong> all the three phases of 400kV system for around 9 seconds. The bus voltagerecovers after the cascade tripp<strong>in</strong>g.Figure 59: Dip <strong>in</strong> voltage at Moga dur<strong>in</strong>g disturbance <strong>in</strong> Punjab systemFigure 60: Increase <strong>in</strong> frequency dur<strong>in</strong>g the <strong>in</strong>cident <strong>in</strong> Punjab due to loss of loadPOSOCO Page 73 of 143