<strong>Procedure</strong>Fiberglass conduit and sweeps must be blackwith three red stripes to identify electricconductors inside. For complete specificationson fiberglass conduit request a copy ofmaterial specification ZG033, or find thisspecification at www.rockymountain.net/ESRFigure 2.2.5.1 – Fiberglass <strong>Conduit</strong>Figure 2.2.5.2 – Electrical Grade PVCFigure 2.2.5.3 – Fiberglass SweepsAdditional conduit and sweep requirements and comments:• PVC shall be electrical grade 40 or better• Fiberglass conduit shall meet or exceed the Power Company’s materialspecification ZG033J:\Publications\FPP\DIS\PRO\<strong>242</strong>-<strong>RMP</strong> <strong>Underground</strong> <strong>Conduit</strong> <strong>System</strong>s.docx R6, 5/13/14This document is posted online at rockymountainpower.net, and at engineering’s intranet site for distribution procedures.Modification of this document must be authorized by PacifiCorp engineering publications, (503) 813-5293. 6