6.3 Installing <strong>Conduit</strong> through PavementFor conduit through pavement or concrete requirements, see section 2.2.11, <strong>Conduit</strong>through Pavement.<strong>Procedure</strong>Figure 6.3 – Installing <strong>Conduit</strong> through Concrete6.4 Pull Line, Proofing, and Sealing the <strong>Conduit</strong>For conduit sealing and pull line requirements, see sections 2.2.3, Dirt and Debrisand 2.2.4, Pull Rope. For conduit proofing requirements, see section 2.2.7, <strong>Conduit</strong>Proofing.<strong>Conduit</strong> plugA pull line capable ofwithstanding 500 lbs. oftension, installed withsix feet of extra lineextending from eachend of the conduit. Thepull line shall be securedbefore the ends areplugged.Figure 6.4.1 – <strong>Conduit</strong> Plug and Pull LineJ:\Publications\FPP\DIS\PRO\<strong>242</strong>-<strong>RMP</strong> <strong>Underground</strong> <strong>Conduit</strong> <strong>System</strong>s.docx R6, 5/13/14This document is posted online at rockymountainpower.net, and at engineering’s intranet site for distribution procedures.Modification of this document must be authorized by PacifiCorp engineering publications, (503) 813-5293. 25