2.2.7 <strong>Conduit</strong> ProofingAll underground runs shall be proofed with a mandrel to removeobstructions, and to confirm at least 80 percent of the nominal conduitdiameter. When requested by the Power Company, the customer shallperform a Power Company witnessed proofing of conduit systems. SeeTable 2.2.7, Required Mandrel Sizes for <strong>Conduit</strong> Proofing and Figure 2.2.7.<strong>Procedure</strong>Table 2.2.7 – Required Mandrel Sizes for <strong>Conduit</strong> Proofing<strong>Conduit</strong>NominalDiameter(in.)MandrelDiameter(in.)MinimumMandrelLength(in.)MaximumMandrelLength(in.) Proof (%)2 1.62 2.4 6 813 2.5 3.25 8 834 3.5 4.25 8 876 5.5 6.25 10 923” Mandrel2.5” Diameter4” Mandrel3.5” Diameter6” Mandrel5.5” DiameterFigure 2.2.7 – Typical Mandrels2.2.8 Change in <strong>Conduit</strong> SizeNo change in conduit size within a conduit run is allowed.2.2.9 <strong>Conduit</strong> to Existing EquipmentWhen the customer is installing conduit to existing (energized) equipment,the customer shall stop installation of the conduit two feet from the PowerCompany facility, unless otherwise requested by the Power Company. TheJ:\Publications\FPP\DIS\PRO\<strong>242</strong>-<strong>RMP</strong> <strong>Underground</strong> <strong>Conduit</strong> <strong>System</strong>s.docx R6, 5/13/14This document is posted online at rockymountainpower.net, and at engineering’s intranet site for distribution procedures.Modification of this document must be authorized by PacifiCorp engineering publications, (503) 813-5293. 8

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!