Notes:For each conduit run:•2’ of trench left open•90° elbow permanentlyattached to each conduit runExcavation depth should be 10” plus thesize of the largest conduit (3” – 4”).2'LegendOpen ExcavationBackfill<strong>Conduit</strong>3/4” minus leftfor leveling<strong>Procedure</strong>Not drawn to scale4'Trench<strong>Conduit</strong>90° elbow2’4'Figure 11.4.1 - Top View - Secondary BoxNotes:All conduits need to come up into the center of theexcavation where the pad box will be placed.The Power Company will cut the elbows as needed.Final GradeMinimum depth =10” + conduitdiameterFigure 11.4.2 - Side View - <strong>Conduit</strong> Placement - Secondary BoxJ:\Publications\FPP\DIS\PRO\<strong>242</strong>-<strong>RMP</strong> <strong>Underground</strong> <strong>Conduit</strong> <strong>System</strong>s.docx R6, 5/13/14This document is posted online at rockymountainpower.net, and at engineering’s intranet site for distribution procedures.Modification of this document must be authorized by PacifiCorp engineering publications, (503) 813-5293. 52