• • • • •RSVIEW SUPERVISORY EDITION USER’S GUIDEThresholdvaluesThresholdsAlarmseveritylevels5,0006*1Increasing4,0005*43,000482,00038Safe zoneDecreasing1,00026114TimeThresholds must be set upin ascending order* These alarms are triggered only if Generate alarms whenapproaching normal operating range is selected in the AlarmSetup dialog box.If the motor speedIt triggers an alarm of this severityexceeds 3,000 rpm 8exceeds 4,000 rpm 4exceeds 5,000 rpm 1falls below 5,000 rpm* 4falls below 4,000 rpm* 8falls below 2,000 rpm 8falls below 1,000 rpm 6falls below 1 rpm 4In the illustration, an X shows when the tag goes into alarm and an O shows when the taggoes out of alarm.Alarms occur when the motor speed falls below 5,000 rpm and 4,000 rpm, and when itrises above 1 rpm and 1,000 rpm. These alarms would not occur if Generate alarms whenapproaching normal operating range was cleared in the Alarm Setup dialog box11-4