• • • • •RSVIEW SUPERVISORY EDITION USER’S GUIDESet up alarmseverities.Create alarmmessages toreplace the systemmessages.For details about using the Alarm Setup editor, see Help.Setting up alarm monitoringIn the Setup tab of the Alarm Setup editor you can specify:• how the system behaves when alarms cross back over trigger thresholds.• how often the system checks for new alarms.• where alarms are logged and printed when HMI-server redundancy is turned on.Alarm trigger thresholdsAn alarm is triggered when the value of an analog tag crosses its alarm threshold. If thevalue of the tag fluctuates above and below its alarm threshold, alarms are triggered eachtime the tag value rises above the threshold value, or falls below the threshold value. Youcan enable or disable this feature.For more information about how this feature works, see “Thresholds” on page 11-3.Specifying how often the system checks for alarmsThe system does not check for alarms more frequently than the maximum update ratespecified in the Alarm Setup dialog box. You should match the maximum update rate tothe rate at which you expect tag values to change. For example, if you are monitoring11-16