Chapter 4 Software Index<br />
1-01 = 0002, Control mode is as below:<br />
(1). Input signal is NPN: (2). Input signal is PNP:<br />
S1 (run)<br />
S2 (stop)<br />
S3 (FWD/REV)<br />
COM<br />
Note: As 3 wire control mode is selected, the terminal S3 is not controlled by 5-02.<br />
Note: 1-02=0001, the reverse command is unavailable.<br />
1-02 : Prohibition of Reverse Operation 0000: Enable Reverse Command<br />
0001: Disable Reverse Command<br />
1-02=0001, the reverse command is invalid.<br />
1-03 : Keypad Stop Button 0000: Stop Button Enable<br />
0001: Stop Button Disable<br />
1-03=0000, the STOP key is available for controlling the inverter to stop.<br />
※Note: 1-03=0001 is valid only for 1-00 = 0001 and 0002,<br />
1-04 : Starting Method Selection 0000: Normal Start<br />
0001: Enable Speed Search<br />
1.) 1-04=0000: As starting, the inverter accelerates from 0 to target frequency in the set time.<br />
2.) 1-04=0001: As starting, the inverter accelerates to target frequency from the detected speed of<br />
motor.<br />
1-05 : Stopping Method 0000: Controlled Deceleration-to- Stop with DC Injection Braking<br />
(Rapid Stop)<br />
0001: Free run stop<br />
1.) 1-05=0000: the inverter will decelerate to 0Hz in preset deceleration time after receiving the stop<br />
4-23<br />
S1 (run)<br />
S2 (stop)<br />
S3 (FWD/REV)<br />
24V(common)