Chapter 4 Software Index<br />

External switch terminal is OFF: in communication, the master (PC or PLC) can control the<br />

inverter operation and frequency signal and allowably modify the parameters, and the operation<br />

signals from Keypad and TM2 are idle. Furthermore, the keypad can only display the voltage,<br />

current and frequency, the parameters are readable and not writable, and Emergency Stop is<br />

valid.<br />

External switch terminal is ON: in communication, the inverter is controlled by the keypad<br />

regardless of the setting of 1-00/1-06 and master. Under such circumstance, the master still can<br />

read and write the inverter parameters.<br />

11. 5-00~06=13: Disable acceleration and deceleration<br />

The acceleration and deceleration action is unavailable till the forbid acceleration and<br />

deceleration signals are released. The action is illustrated in the graph below:<br />

Operation<br />

Signal<br />

Disable<br />

ACC/DEC<br />

Output<br />

Frequency<br />

12. 5-00~06=14,15: UP / DOWN Function (Actual ACC/DEC time is base on the setting):<br />

(1)Please set 1-06 = 3 if you want to use the UP/DOWN Function, and the other frequency signals<br />

are useless.<br />

(2)Set 5-08 = 0 and 5-09 = 0, the inverter accelerates to the preset value of 6-00 when the<br />

operation terminal is ON. Then, it maintains the certain speed. As the inverter receives the<br />

UP/DOWN command, it will accelerate / decelerate till the command is released. The<br />

inverter runs at the certain speed. The inverter will ramp stop or Free-Fun stop which is<br />

determined by the 1-05 as long as the inverter receives the STOP command. And the<br />

frequency of Stopping will be stored in 6-00. The UP/DOWN KEY is invalid as the inverter<br />

stops. It is necessary to use the Keypad to modify the preset parameter.<br />

(3)Set 5-08 = 1, the inverter will operate from 0Hz when the operation terminal is ON. The<br />

action of UP/DOWN is as above description. The inverter will ramp stop or free-run stop<br />

which determined by1-05 setting when as it receiving the Stop Command and back to 0Hz.<br />

The next operation will start at 0 Hz.<br />

(4) That UP/Down Signal Simultaneously act are invalid<br />

(5) 5-09≠ 0, the inverter will accelerate to the setting of 6-00 and maintain at the speed. When<br />

the UP/Down terminal is On, setting frequency is present value 6-00±5-09, and the inverter<br />

will accelerate/ decelerate to frequency 6-00. The upper frequency limit and lower frequency<br />

limit also restrict the operation. If the signal of UP/ DOWN is maintained over 2 seconds, the<br />

inverter will begin to accelerate/ decelerate. If 5-09=0, the operation is the same, till the UP/<br />

DOWN signal stops. Please refer to the time diagram of 5-09.<br />

4-36<br />

※Note: Operation Switch is OFF,<br />

the command of disable