4-34<br />

Chapter 4 Software Index<br />

Parameter Group 5-Multifunction Input Terminals (MFIT)<br />

Multifunction input terminals (TM2 S1-S6/AIN) controlling:<br />

5-00~06 0000: Forward/Stop Command * 1<br />

0001: Reverse/Stop Command * 2<br />

0002: Preset Speed # 1 (6-02)<br />

0003: Preset Speed # 2 (6-03)<br />

0004: Preset Speed # 3 (6-05) * 3<br />

0005: Jog<br />

0006: Acc/Dec time # 2<br />

0007: Emergency Stop Contact A<br />

0008: Base Block<br />

0009: Speed Search Stop<br />

0010: Energy Saving<br />

0011: Control Signal Selection<br />

0012: Communication Control Signal Selection<br />

0013: Acc/Dec Disabled<br />

0014: Up Command<br />

0015: Down Command<br />

0016: Principal/Auxiliary Speed<br />

0017: PID Function Disabled<br />

0018: Reset<br />

0019: Encoder Input Terminal(Terminal S5)<br />

0020: PID Feedback Signal A12 (Terminal S6)<br />

0021: AI2 Bias Signal 1 Input(Terminal S6)<br />

0022: AI2 Bias Signal 2 Input(Terminal S6)<br />

0023: Analog Input(Terminal AIN)<br />

0024: PLC Application<br />

0025: Traverse Run<br />

0026: Traverse Run Upper Deviation<br />

0027: Traverse Run Lower Deviation<br />

0028: Power Source Detect for KEB Function<br />

0029: Emergency Stop Contact B<br />

A. The terminals S1-AIN on terminal block (TM2) are multifunction input terminals. The above 30<br />

functions can be set in these terminals.<br />

B. Function Description for 5-00~06:<br />

1. 5-00~06=0/1(Forward/Reverse/Stop)<br />

As forward command is ON, the inverter runs while stops as OFF. The 5-00 factory set is<br />

forward.<br />

As reverse command is ON, the inverter runs while stops as OFF. The 5-01factory set is<br />

reverse.<br />

2. 5-00~06=2-4(Preset speed 1~3)<br />

External multifunction input terminals are ON, the inverter is operation at the preset time, and<br />

the duration is determined by the time of the terminal ON. The corresponding frequency<br />

parameter is illustrated below: