4-34<br />
Chapter 4 Software Index<br />
Parameter Group 5-Multifunction Input Terminals (MFIT)<br />
Multifunction input terminals (TM2 S1-S6/AIN) controlling:<br />
5-00~06 0000: Forward/Stop Command * 1<br />
0001: Reverse/Stop Command * 2<br />
0002: Preset Speed # 1 (6-02)<br />
0003: Preset Speed # 2 (6-03)<br />
0004: Preset Speed # 3 (6-05) * 3<br />
0005: Jog<br />
0006: Acc/Dec time # 2<br />
0007: Emergency Stop Contact A<br />
0008: Base Block<br />
0009: Speed Search Stop<br />
0010: Energy Saving<br />
0011: Control Signal Selection<br />
0012: Communication Control Signal Selection<br />
0013: Acc/Dec Disabled<br />
0014: Up Command<br />
0015: Down Command<br />
0016: Principal/Auxiliary Speed<br />
0017: PID Function Disabled<br />
0018: Reset<br />
0019: Encoder Input Terminal(Terminal S5)<br />
0020: PID Feedback Signal A12 (Terminal S6)<br />
0021: AI2 Bias Signal 1 Input(Terminal S6)<br />
0022: AI2 Bias Signal 2 Input(Terminal S6)<br />
0023: Analog Input(Terminal AIN)<br />
0024: PLC Application<br />
0025: Traverse Run<br />
0026: Traverse Run Upper Deviation<br />
0027: Traverse Run Lower Deviation<br />
0028: Power Source Detect for KEB Function<br />
0029: Emergency Stop Contact B<br />
A. The terminals S1-AIN on terminal block (TM2) are multifunction input terminals. The above 30<br />
functions can be set in these terminals.<br />
B. Function Description for 5-00~06:<br />
1. 5-00~06=0/1(Forward/Reverse/Stop)<br />
As forward command is ON, the inverter runs while stops as OFF. The 5-00 factory set is<br />
forward.<br />
As reverse command is ON, the inverter runs while stops as OFF. The 5-01factory set is<br />
reverse.<br />
2. 5-00~06=2-4(Preset speed 1~3)<br />
External multifunction input terminals are ON, the inverter is operation at the preset time, and<br />
the duration is determined by the time of the terminal ON. The corresponding frequency<br />
parameter is illustrated below: