4-44<br />
Chapter 4 Software Index<br />
Parameter Group 8 - Multifunction output terminal and output signal<br />
operation mode<br />
Multifunction analog output control:<br />
8-00: Analog Output Voltage Mode:<br />
0000: Output frequency<br />
0001: Frequency Setting<br />
0002: Output voltage<br />
0003: DC Bus Voltage<br />
0004: <strong>Motor</strong> current<br />
0005: FEEDBACK Signal of PID<br />
8-01: Analog Output Gain = 0 ~ 200%<br />
The multifunction analog output terminal of the terminal block (TM2), is 0~10Vdc analog output. The<br />
output type is determined by the 8-01. The function of 8-01 is: when there is tolerance for the external<br />
voltage meter and peripheral equipment, please regulate 8-00.<br />
The FEEDBACK value of PID (That is the input voltage and current of S6) outputs analog value from<br />
FM+ terminal. (Decide to parameter 4-06) The value is corresponding to the input signal 0~10V (0 ~<br />
20 mA) or 2~10V (4~20mA).<br />
※Note: The max output voltage is 10V due to the circuit, even the output voltage should be higher than<br />
10V.<br />
Multifunction output terminals control:<br />
8-02: RELAY1(R1C,R1B,R1A terminal on TM2)<br />
8-03: RELAY2(R2C,R2A terminal on TM2)<br />
0000: Run<br />
0001: Frequency Reached (Target Frequency) (Set Frequency ± 8-05)<br />
0002: Set Frequency (8-04 ± 8-05)<br />
0003: Frequency Threshold Level (> 8-04) - Frequency Reached<br />
0004: Frequency Threshold Level (< 8-04) - Frequency Reached<br />
0005: Over torque Threshold Level<br />
0006: Fault<br />
0007: Auto-restart<br />
0008: Momentary AC Power Loss<br />
0009: Rapid Stop Mode (When multifunction input set to 0007)<br />
0010: Coast-to-Stop Mode (When multifunction input set to 0008)<br />
0011: <strong>Motor</strong> Overload Protection<br />
0012: Drive Overload Protection<br />
0013: PID Feedback Signal Break<br />
0014: PLC Operation<br />
0015: Power On