9-03 (Trip DEC Level)<br />
9-04 (Trip RUN Sel)<br />
9-05 (Trip Run Level)<br />
9-06 (Dec Sel Trip RUN)<br />
9-07<br />
(Dec Time Trip<br />
RUN)<br />
9-08 (<strong>Motor</strong> OL1 Sel)<br />
Trip Prevention Level During<br />
Deceleration (%)<br />
Trip Prevention Selection in<br />
Run Mode<br />
Trip Prevention Level In Run<br />
Mode (%)<br />
Trip Prevention Deceleration<br />
Time Selection in Run Mode<br />
Deceleration Time In Trip<br />
Prevention Mode (Seconds)<br />
Electronic <strong>Motor</strong> Overload<br />
Protection Operation Mode<br />
9-09 (<strong>Motor</strong> Type) <strong>Motor</strong> type Selection<br />
9-10 (<strong>Motor</strong> OL1 Curve)<br />
9-11 (<strong>Motor</strong> OL1 Operat)<br />
<strong>Motor</strong> Overload Protection<br />
Curve Selection<br />
Operation After Overload<br />
Protection is Activated<br />
9-12 (Torq Det Sel) Over torque Detection Selection<br />
9-13 (Torq Det Operat)<br />
9-14 (Torq Det Level)<br />
9-15 (Torq Det Delay)<br />
Operation After Over torque<br />
Detection is Activated<br />
Over torque Threshold Level<br />
(%)<br />
Over torque Activation Delay<br />
Time (Seconds)<br />
4-17<br />
Chapter 4 Software Index<br />
200<br />
50 - 300<br />
150*9<br />
0000: Enable Trip Prevention in Run<br />
Mode<br />
0000<br />
0001: Disable Trip Prevention in<br />
Run Mode<br />
200<br />
50 - 300<br />
150*9<br />
0000: Trip Prevention Deceleration<br />
Time Set by 3-03<br />
0000<br />
0001: Trip Prevention Deceleration<br />
Time Set by 9-07<br />
0.1 – 3600.0 3.0<br />
0000: Enable Electronic <strong>Motor</strong><br />
Overload Protection<br />
0001: Disable Electronic <strong>Motor</strong><br />
Overload Protection<br />
0000: Electronic <strong>Motor</strong> Overload<br />
Protection Set for<br />
Non-Inverter Duty <strong>Motor</strong><br />
0001: Electronic <strong>Motor</strong> Overload<br />
Protection Set for Inverter<br />
Duty <strong>Motor</strong><br />
0000: Constant Torque (OL =103 %)<br />
(150 % for 1 Minute)<br />
0001: Variable Torque (OL = 113 %)<br />
(123 % for 1 Minute)<br />
0000: Coast-to-Stop After Overload<br />
Protection is Activated<br />
0001: Drive Will Not Trip when<br />
Overload Protection is<br />
Activated (OL1)<br />
0000: Disable Over torque Operation<br />
0001: Enable Over torque Operation<br />
Only if at Set Frequency<br />
0002: Enable Over torque Operation<br />
while the Drive is in Run<br />
Mode<br />
0000: Drive will Continue to<br />
Operate After Over torque is<br />
Activated<br />
0001: Coast-to-Stop After Over<br />
torque is Activated<br />
0000<br />
0000<br />
0000<br />
0000<br />
0000<br />
0000<br />
30 - 200 160<br />
0.0 - 25.0 0.1