Chapter 4 Software Index<br />
190V(220V system)or 380V(440V system).<br />
3.When KEB function enabled,the inverter decelerate to zero by 2-08,and the inverter stop.<br />
4.IF the power on signal enabled during the KEB function ,the inverter accelerate to original<br />
frequency.<br />
Parameter Group 3 - Operating Parameters<br />
3-00: Frequency Upper limit(Hz) : 0.01 - 650.00<br />
3-01: Frequency Lower limit(Hz) : 0.01 - 650.00<br />
Internal frequency<br />
3-00 (upper frequency limit)<br />
3-01 (lower frequency limit)<br />
(note)<br />
※Note: When 3-01 = 0 Hz and frequency command is 0 Hz, the inverter will stop at 0 speed.<br />
When 3-01 > 0 Hz and frequency command ≦3-01, the inverter will output 3-01 preset<br />
value.<br />
3-02 : Acceleration Time #1 (second): 0.1 – 3600.0<br />
3-03 : Deceleration Time #1 (second): 0.1 – 3600.0<br />
3-04 : S Curve of First Acceleration Stage (second): 0.0 – 4.0<br />
3-05 : S Curve of Second Acceleration Stage (second): 0.0 – 4.0<br />
3-06 : Acceleration Time #2 (second): 0.1 – 3600.0<br />
3-07 : Deceleration Time #2 (second): 0.1 – 3600.0<br />
3-08 : Jog Acceleration Time (second): 0.1 –25.5<br />
3-09 : Jog Deceleration Time (second): 0.1 – 25.5<br />
1.) Formula for calculating acceleration and deceleration time: The denominator is base on the<br />
rated frequency of motor.<br />
Preset frequency Preset frequency<br />
Acceleration time = 3-02 (or 3-06) x<br />
,Deceleration time = 3-03 (or 3-07) x<br />
0-05<br />
0-05<br />
2.)When 5-00 – 5-06 is set 06 (the second acceleration and deceleration time), the first<br />
acceleration/ deceleration/ S curve or the second acceleration/ deceleration/ S curve will be<br />
selected by off or on the external input terminal.<br />
3.) When 5-00 – 5-06 is set 05 (Jog), Jog run is controlled by external terminals. The acceleration<br />
and deceleration action will be at Jog acceleration and deceleration time.<br />
4.)When 5-00 – 5-06 is set as 05(Jog) and 06(acceleration and deceleration time toggle), to<br />
change the acceleration and deceleration time by ON the external terminals, and the list<br />
setting:<br />
Function Acc/ Dec time 1(3-02/3-03) Acc/ Dec time 2 (3-06/3-07) JOG Acc/Dec time (3-08/3-09)<br />
1-06 determines the output 1-06 determines the output<br />
preset value<br />
Run at 6-01Jog frequency<br />
frequency<br />
frequency<br />
4-27