3-17: Parameter lock function<br />
0000: Enable all Functions<br />
0001: 6-00 - 6-08 cannot be changed<br />
0002: All Functions Except 6-00 - 6-08 cannot be changed<br />
0003: Disable All Function<br />
Chapter 4 Software Index<br />
3-18: Copy Unit<br />
0000: Disable<br />
0001: Inverter to Copy Unit<br />
0002: Copy Unit to Inverter<br />
0003: Verify<br />
1.) 3-18=0000: Inverter can not copy parameter.<br />
2.) 3-18=0001: Copy the inverter parameters to module.<br />
3.) 3-18=0002: Copy the module parameters to inverter.<br />
4.) 3-18=0003: Copy the parameters to inverter or module to mutually verify the parameters.<br />
※Note: The copy function is available for the models with same capacity.<br />
3-19: Fan Running Controlling<br />
0000: Auto (Depend on temp.)<br />
0001: Operate while in RUN Mode<br />
0002: Always Run<br />
0003: Always Stop<br />
1.) 3-19=0000: The fan run as the inverter senses temperature rises. Thusly, extend the service<br />
period.<br />
2.) 3-19=0001: The fan runs while the inverter is running.<br />
3.) 3-19=0002: The fan is continuously running regardless of the action of the inverter.<br />
4.) 3-19=0003: The fan is always stopping regardless of the action of the inverter.<br />
※Note: Depend on the hardware, the function is disable at 15HP above of 220V class and 20HP<br />
above of 440V class. The fan is running after the inverter power on.<br />
3-20: Energy Saving Mode Operation 0000: Disabled<br />
0001: Controlled by MFIT at Set Frequency<br />
3-21: Energy saving operation gain (%): 0-100<br />
1.) In terms of FAN, PUMP or other heavy inertia loads which need greater start torsion, while in<br />
operation they need not so high torsion. Consequently, to decline the output voltage to saving<br />
energy by setting 3-20 is necessary.<br />
2.) 5-00 ~5-06(Multifunction input terminal) set as10 to saving energy.