command.<br />
4-24<br />
Chapter 4 Software Index<br />
2.) 1-05=0001: the inverter will stop output as receiving the stop command. The motor will inertia<br />
free run to stop.<br />
1-06 : Frequency Command Source Selection<br />
0000: Set the Frequency with Keypad<br />
0001: Potentiometer on Keypad<br />
0002: External Analog Signal Input or Remote Potentiometer<br />
0003: Up/Down Frequency Control Using MFIT (S1 - S6)<br />
0004: Communication Setting Frequency<br />
0005: Impulse frequency (S5) setting frequency (ver2.3)<br />
1.) 1-06=0001, as one of the parameter in group 5-00~ 5-06is set 16 and multifunction terminal is<br />
OFF, the frequency is set by the KNOB(VR for principal speed) on keypad. While the<br />
multifunction is ON, the frequency is set by analog signal (auxiliary speed) on terminal block<br />
(TM2).<br />
2.) 1-06=0002, as one of the parameter in group 5-00~ 5-06 is set 16 and the multifunction terminal<br />
is OFF, he frequency is set by analog signal (principal speed) on terminal block (TM2), While<br />
the multifunction is ON, the frequency is set by the KNOB(VR for auxiliary speed) on keypad.<br />
3.) Please refer to description of parameter group 5-00~ 5-06 (multifunction input terminals) for the<br />
function Up/Down terminal.<br />
4.) The priority in reading frequency is PLC frequency control >traverse run >Jog> preset<br />
speed>▲▼ on keypad or Up / Down or communication control.<br />
5.) Impulse frequency command input source should be setting as S5 terminal and need to<br />
coordinate with 5-10 frequency exchange times ratio. For example, the input value S5 is 4KHZ,<br />
5-10 is 1.500 times, and output frequency is 40.00*1.5=60.00HZ. 5-04(S5) should be setting as<br />
19.<br />
1-07:Keypad Operation with Up/Down Keys in Run Mode<br />
0000: ‘Enter’ must be pressed after frequency change with Up/Down Keys on keypad.<br />
0001: Frequency will be changed directly when Up/Down Keys are Pressed