Chapter 4 Software Index<br />

3.) 3-20=0001, If the multifunction terminal is set as 10(energy saving control terminal), the output<br />

voltage will gradually decline to ‘original voltage’ב3-21’ preset value as the terminal’ is ON.<br />

The output voltage will rise to original voltage as the terminal is OFF.<br />

※Note:1.The declining and rising speeds of voltage for energy saving is same as the ones for<br />

SPEED SEARCH.<br />

2. Energy saving mode is only available under V/F mode. (0-00 = 0002).<br />

3-22: Carrier Frequency (KHz) : 2-16<br />

3-22<br />

Carrier<br />

Frequency<br />

3-22<br />

Carrier<br />

Frequency<br />

3-22<br />

Carrier<br />

Frequency<br />

3-22<br />

Carrier<br />

Frequency<br />

2 2KHz 6 6KHz 10 10KHz 14 14KHz<br />

3 3KHz 7 7KHz 11 11KHz 15 15KHz<br />

4 4KHz 8 8KHz 12 12KHz 16 16KHz<br />

5 5KHz 9 9KHz 13 13KHz<br />

※Note: The external electronic components maybe interfered, more serious, even the motor<br />

vibration due to cutting of the high carrier frequency waveform, although the inverter<br />

provides low noise environment in running. Thusly, it is necessary to regulate the carrier<br />

frequency.<br />

3-23 : Center Frequency (CF) of Traverse Run(%): 2-16<br />

3-24 : Amplitude(%): 0.1-20.0<br />

3-25 : Amplitude Drop(%) : 0.0-50.0<br />

3-26 : Acceleration Time (s) : 0.5-60.0<br />

3-27 : Deceleration Time (s) : 0.5-60.0<br />

3-28 : Deviated traverse(X upper deviation) (%) : 0.0-20.0<br />

3-29 : Deviated traverse(Y lower deviation) (%) : 0.0-20.0<br />

Traverse Run is defined as adding a triangle wave to the basic operation frequency of inverter output<br />

frequency at the preset acceleration and deceleration time. The action is as the graph below:<br />

3-23: Traverse Run Center frequency(%)<br />

3-24: Amplitude(%)<br />

3-25: Amplitude Drop(%)<br />

3-26: Acceleration Time (s)<br />

3-27: Deceleration Time (s)<br />

3-28: Deviated traverse<br />

(X upper deviation)<br />

Fout<br />

3-23<br />

3-24<br />

3-25<br />

3-28<br />

3-29<br />

3-29: Deviated traverse<br />

3-26 3-27<br />

(Y lower deviation)<br />

0 Time<br />

1) The traverse run is available as the run command and the terminal (5-00~5-05=0025) for such<br />

operation both ON. Inverter operating, the traverse run is ready when the inverter output<br />

frequency reaches center frequency (3-23). During acceleration to center frequency, the<br />

acceleration time is at the originally preset value (3-02/3-06). When the traverse run is OFF or the<br />

Inverter is OFF, the deceleration time is also at original preset value (3-03/3-07). However, in<br />

Fout<br />

3-25<br />

4-30<br />

Traverse run