Chapter 4 Software Index<br />
C<br />
0 / 9 50.0% 1.0%<br />
1 / 10 60.0% 1.0%<br />
2 / 11 65.0% 1.0%<br />
3 / 12 70.0% 1.0%<br />
4 / 13 40.0% 1.0%<br />
5 / 14 35.0% 1.0%<br />
6 / 15 45.0% 1.0%<br />
7 / 16 55.0% 1.0%<br />
8 / 17 65.0% 1.0%<br />
3. The inverter will output the value that B, C voltage (refer to 10-0) plus 10-1 V/F pattern setting.<br />
And the start torque will be raised.<br />
10-1=<br />
100%<br />
1<br />
25/3<br />
※Note: 10-1=0, Torque boost function is invalid<br />
4. When the induction motor is in running, there must be slip due to the load. It is necessary to boost to<br />
improve the precision of the speed.<br />
Output Current-(10-2) Note : 0-02=motor rated current<br />
Slip frequency boost =<br />
× (10-3)<br />
(0-02)-(10-2)<br />
10-2=motor no load current<br />
10-3 rough value= (<strong>Motor</strong> synchronization speed– Rated speed) / <strong>Motor</strong> synchronization speed<br />
Marked on the motor nameplate<br />
<strong>Motor</strong> synchronization speed (RPM)=<br />
120<br />
<strong>Motor</strong> Poles<br />
× <strong>Motor</strong> rated frequency (50Hz or 60Hz)<br />
eg: 4 Poles,60Hzinduction motor synchronization speed =<br />
B<br />
C<br />
Voltag<br />
4-52<br />
120<br />
4<br />
× 60=1800 RPM<br />
※Note: <strong>Motor</strong> no load current(10-2) differs with the inverter capacities(15-0)(Refer to 0-02 note),<br />
It should be regulated according to the actual condition.<br />
50/6<br />
Hz