CV7300 Instruction Manual - TECO-Westinghouse Motor Company
CV7300 Instruction Manual - TECO-Westinghouse Motor Company
CV7300 Instruction Manual - TECO-Westinghouse Motor Company
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
5- Multifunction Input Terminals (MFIT)<br />
Function<br />
Code No.<br />
LCD<br />
Display<br />
Description Range/Code<br />
4-14<br />
Chapter 4 Software Index<br />
0000: Forward/Stop Command *<br />
5-00 (MFIT S1 Sel) Multifunction Input Term. S1 0000<br />
5-01 (MFIT S2 Sel) Multifunction Input Term. S2 0001<br />
5-02 (MFIT S3 Sel) Multifunction Input Term. S3 0002<br />
5-03 (MFIT S4 Sel) Multifunction Input Term. S4 0003<br />
5-04 (MFIT S5 Sel) Multifunction Input Term. S5 0004<br />
5-05 (MFIT S6 Sel) Multifunction Input Term. S6 0018<br />
5-06 (MFIT AIN Sel) Multifunction Input Term. AIN<br />
1<br />
0001: Reverse/Stop Command * 2<br />
0002: Preset Speed # 1 (6-02)<br />
0003: Preset Speed # 2 (6-03)<br />
0004: Preset Speed # 3 (6-05) * 3<br />
0005: Jog<br />
0006: Acc/Dec # 2<br />
0007: Emergency Stop A Contact<br />
0008: Base Block<br />
0009: Speed Search<br />
0010: Energy Saving<br />
0011: Control Signal Selection<br />
0012: Communication Selection<br />
0013: Acc/Dec Disabled<br />
0014: Up Command<br />
0015: Down Command<br />
0016: Master/Auxiliary Speed<br />
0017: PID Function Disabled<br />
0018: Reset<br />
0019: Encoder input terminal<br />
( terminal S5 )<br />
0020: PID feedback signal A12<br />
( terminal S6)<br />
0021: AI2 Bias signal 1 input<br />
(terminal S6)<br />
0022: AI2 Bias signal 2 input<br />
(terminal S6)<br />
0023: Analog input(terminal AIN)<br />
0024: PLC Application<br />
0025: Traverse Run<br />
Multifunction Input Term. S1 -<br />
0026: Traverse run upper deviation<br />
0027: traverse run lower deviation<br />
0028: Power Source Detect for KEB<br />
Function<br />
0029: Emergency Stop B Contact *7<br />
0023<br />
5-07 (MFIT Scan Time) S6 Signal Verification Scan<br />
Time (mSec X 4 )<br />
1 – 100 5<br />
Factory<br />
Setting Remarks