<strong>Grundfos</strong> E-<strong>pumps</strong><br />
3<br />
Setting up the pump<br />
Factory setting<br />
Pumps without factory-fitted sensor<br />
The <strong>pumps</strong> have been factory-set to control mode<br />
"Uncontrolled".<br />
The setpoint value corresponds to 100 % of the maximum<br />
pump performance. See pump performance<br />
curve.<br />
Pumps with pressure sensor<br />
The <strong>pumps</strong> have been factory-set to control mode<br />
"Controlled". The setpoint value corresponds to 50 %<br />
of the sensor measuring range (see sensor nameplate).<br />
Setpoint setting<br />
Set the desired setpoint by pressing or .<br />
The light fields on the control panel will indicate the<br />
setpoint set.<br />
Pump in control mode "Controlled" (pressure<br />
control)<br />
Example<br />
Figure 27 shows that the light fields 5 and 6 are yellow,<br />
indicating a desired setpoint of 3 bar (43.5 psi).<br />
The setting range is equal to the sensor measuring<br />
range (see sensor nameplate).<br />
6<br />
[bar]<br />
E-<strong>pumps</strong><br />
Setting via the control panel<br />
The pump control panel (fig. 25 or 26) incorporates the<br />
following buttons and indicator lights:<br />
• buttons, and , for setpoint setting<br />
• light fields, yellow, for indication of setpoint<br />
• indicator lights, green (operation) and red (fault).<br />
Light fields<br />
Buttons<br />
3<br />
0<br />
Fig. 27 Setpoint set to 3 bar (pressure control)<br />
Pump in control mode "Uncontrolled"<br />
TM00 7743 0904<br />
Example<br />
In control mode "Uncontrolled", the pump performance<br />
is set within the range from min. to max. curve.<br />
See fig. 28.<br />
Indicator lights<br />
TM00 7600 0304<br />
H<br />
Fig. 25 Control panel, single-phase <strong>pumps</strong>, .5 Hp - 1.5 Hp<br />
(0.37 kW - 1.1 kW)<br />
Light fields<br />
Buttons<br />
Q<br />
TM00 7746 1304<br />
Fig. 28 Pump performance setting, control mode<br />
"Uncontrolled"<br />
Indicator lights<br />
TM02 8513 0304<br />
Fig. 26 Control panel, three-phase <strong>pumps</strong>, 1 Hp -30 Hp<br />
(0.75 - 22 kW)<br />
25