Warning and alarm list<br />

Fault<br />

code<br />

Single phase MLE Three phase MLE Warning Alarm<br />

3 External fault External fault ●<br />

4 Too many restarts Too many restarts ●<br />

7 Too many restarts ●<br />

30 Replace motor bearings ●<br />

31 Replace varistor* ●<br />

32 Overvoltage Overvoltage ●<br />

40 Undervoltage Undervoltage ●<br />

41 Undervoltage transient ●<br />

45 Mains asymmetry ●<br />

49 Overload Overload ●<br />

51 Blocked motor ●<br />

55 Motor current protection Motor current protection ●<br />

56 Underload ●<br />

57 Dry run ●<br />

65 Motor temperature protection Motor temperature protection ●<br />

73 Hardware shutdown Hardware shutdown ●<br />

76 Internal communication error ●<br />

77 Duty/Standby communication error ●<br />

85 Unrecoverable EEPROM fault Unrecoverable EEPROM fault ●<br />

88 Sensor fault Sensor 1 fault ●<br />

91 Temperature sensor 1 fault ●<br />

93 Sensor 2 fault ●<br />

96<br />

Reference input fault<br />

Common term: “External setpoint fault”<br />

Reference input fault<br />

Common term: “External setpoint fault”<br />

● 1) ● 2)<br />

105 Electronic rectifier protection Electronic rectifier protection ●<br />

106 Electronic inverter protection Electronic inverter protection ●<br />

148 Drive-end bearing temperature ●<br />

149 Non drive-end bearing temperature ●<br />

155 Undervoltage ●<br />

156 Internal communication error ●<br />

175 Temperature sensor 2 fault ●<br />

190 Limit 1 exceeded ●<br />

191 Limit 2 exceeded ●<br />

240 Relubricate motor bearings ●<br />

255 Unknown ●<br />

E-<strong>pumps</strong><br />

*The varistor protects the pump against power supply<br />

transients. If voltage transients occur, the varistor will be worn<br />

over time and need to be replaced. The more transients, the<br />

more quickly the varistor will be worn. A <strong>Grundfos</strong> technician<br />

is required for replacement of the varistor.<br />

1)<br />

Single phase MLE<br />

2)<br />

Three phase MLE<br />

29