Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Grundfos</strong> E-<strong>pumps</strong><br />
5<br />
EMC (electromagnetic compatibility to<br />
EN 61800-3)<br />
Motor<br />
[Hp]<br />
Emission/immunity<br />
1.0 Emission:<br />
1.5<br />
2.0<br />
3.0<br />
5.0<br />
7.5<br />
10<br />
The motors may be installed in residential areas<br />
(first environment), unrestricted distribution, corresponding<br />
to CISPR11, group 1, class B.<br />
Immunity:<br />
The motors fulfill the requirements for both the first and second<br />
environment.<br />
15 Emission:<br />
20 The motors are category C3, corresponding to CISPR11,<br />
25 group 2, class A, and may be installed in industrial areas<br />
(second environment).<br />
30<br />
If fitted with an external <strong>Grundfos</strong> EMC filter, the motors are<br />
category C2, corresponding to CISPR11, group 1, class A,<br />
and may be installed in residential areas (first environment).<br />
When the motors are installed in residential<br />
areas, supplementary measures may be<br />
Note:<br />
required as the motors may cause radio<br />
interference.<br />
Immunity:<br />
The motors fulfill the requirements for both the first and second<br />
environment.<br />
Sound pressure level<br />
Motor<br />
[Hp]<br />
Approvals<br />
Speed stated on the<br />
nameplate<br />
[rpm]<br />
Sound pressure<br />
level<br />
[dB(A)]<br />
1.0<br />
65<br />
1.5 65<br />
2.0 70<br />
3.0 70<br />
5.0 75<br />
7.5 3400-3600<br />
80<br />
10 69<br />
15 70<br />
20 70<br />
25 74<br />
30 78<br />
1 - 10 Hp<br />
15 - 30 Hp<br />
Three-phase MLE motors<br />
For further information about EMC, see section 8. Bus<br />
communication on page 57.<br />
Enclosure class<br />
Standard: IP55 (IEC34-5) (TEFC).<br />
Insulation class<br />
F (IEC 85).<br />
Ambient temperature<br />
During operation: -4 °F to +104 °F (-20 °C to +40 °C)<br />
During storage/transport:<br />
1.0 to 10 Hp: -40°F to +140 °F<br />
(-40 °C to +60 °C)<br />
15 to 30 Hp: -13 °F to +158 °F<br />
(-25 °C to +70 °C)<br />
Relative air humidity<br />
Maximum 95 %.<br />
47