<strong>Grundfos</strong> E-<strong>pumps</strong><br />

3<br />

The functions of the two indicator lights and the signal relay are as shown in the following table:<br />

Fault<br />

(red)<br />

Indicator lights<br />

Operation<br />

(green)<br />

Fault/Alarm,<br />

Warning and<br />

Relubricate<br />

Signal relay activated during:<br />

Operating Ready Pump running<br />

Description<br />

E-<strong>pumps</strong><br />

Off Off The power supply has been switched off.<br />

C<br />

NO NC<br />

C<br />

NO NC<br />

C<br />

NO NC<br />

C<br />

NO NC<br />

Off Permanently on The pump is operating.<br />

C NO NC C NO NC C NO NC C NO NC<br />

Off<br />

Permanently on<br />

C NO NC C NO NC C NO NC C NO NC<br />

The pump has been stopped by the stop<br />

function.<br />

Off Flashing The pump has been set to stop.<br />

C<br />

NO NC<br />

C NO NC C NO NC C NO NC<br />

Permanently on<br />

Permanently on<br />

Off<br />

Permanently on<br />

C NO NC C NO NC<br />

C<br />

NO NC<br />

NO NC<br />

C NO NC C NO NC C NO NC C NO NC<br />

C<br />

The pump has stopped because of a<br />

"Fault"/"Alarm" or is running with a<br />

"Warning" or "Relubricate" indication.<br />

If the pump was stopped, restarting will be<br />

attempted (it may be necessary to restart<br />

the pump by resetting the "Fault"<br />

indication).<br />

If the cause is "External fault", the pump<br />

must be restarted manually by resetting the<br />

"Fault" indication.<br />

The pump is operating, but it has or has had<br />

a "Fault"/"Alarm" allowing the pump to<br />

continue operation or it is operating with a<br />

"Warning" or "Relubricate" indication.<br />

If the cause is "Sensor signal outside signal<br />

range", the pump will continue operating<br />

according to the 70% curve and the fault<br />

indication cannot be reset until the signal is<br />

inside the signal range.<br />

If the cause is "Setpoint signal outside<br />

signal range", the pump will continue<br />

operating according to the min. curve and<br />

the fault indication cannot be reset until the<br />

signal is inside the signal range.<br />

Permanently on<br />

Flashing<br />

C NO NC C NO NC C NO NC C NO NC<br />

The pump has been set to stop, but it has<br />

been stopped because of a "Fault".<br />

Resetting of fault indication<br />

A fault indication can be reset in one of the following<br />

ways:<br />

• Briefly press or on the pump. This will not<br />

change the setting of the pump.<br />

A fault indication cannot be reset by means of or<br />

if the buttons have been locked.<br />

• Switch off the power supply until the indicator lights<br />

are off.<br />

• Switch the external start/stop input off and then on<br />

again.<br />

• Use the R100. See section Fault indications,<br />

page 28.<br />

When the R100 communicates with the pump, the red<br />

indicator light will flash rapidly.<br />

41