31.03.2014 Views

Grundfos E-pumps

Grundfos E-pumps

Grundfos E-pumps

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Grundfos</strong> E-<strong>pumps</strong><br />

3<br />

Speed<br />

Time until relubrication of motor bearings<br />

(only 15-30 Hp)<br />

E-<strong>pumps</strong><br />

Tolerance: ± 5 %<br />

The actual pump speed will appear in this display.<br />

Power input and power consumption<br />

Tolerance: ± 10 %<br />

This display shows the actual pump input power from<br />

the power supply. The power is displayed in W or kW.<br />

The pump power consumption can also be read from<br />

this display. The value of power consumption is an<br />

accumulated value calculated from the pump’s birth<br />

and it cannot be reset.<br />

Operating hours<br />

This display shows when to relubricate the motor bearings.<br />

The controller monitors the operating pattern of<br />

the pump and calculates the period between bearing<br />

relubrications. If the operating pattern changes, the<br />

calculated time until relubrication may change as well.<br />

Displayable values:<br />

• in 2 years<br />

• in 1 year<br />

• in 6 months<br />

• in 3 months<br />

• in 1 month<br />

• in 1 week<br />

• Now!<br />

Time until replacement of motor bearings<br />

(only three-phase <strong>pumps</strong>)<br />

When the motor bearings have been relubricated a<br />

prescribed number of times stored in the controller, the<br />

display in the previous section will be replaced by the<br />

display below.<br />

Tolerance: ± 2 %<br />

The value of operating hours is an accumulated value<br />

and cannot be reset.<br />

Lubrication status of motor bearings<br />

(only 15-30 Hp)<br />

This display shows how many times the motor<br />

bearings have been relubricated and when to replace<br />

the motor bearings.<br />

When the motor bearings have been relubricated,<br />

confirm this action in the INSTALLATION menu.<br />

See Confirming relubrication/replacement of motor<br />

bearings (only three-phase <strong>pumps</strong>), page 37. When<br />

relubrication is confirmed, the figure in the above<br />

display will be increased by one.<br />

This display shows when to replace the motor bearings.<br />

The controller monitors the operating pattern of<br />

the pump and calculates the period between bearing<br />

replacements.<br />

Displayable values:<br />

• in 2 years<br />

• in 1 year<br />

• in 6 months<br />

• in 3 months<br />

• in 1 month<br />

• in 1 week<br />

• Now!<br />