8<br />

8. Bus communication<br />

Bus communication with E-<strong>pumps</strong><br />

All <strong>Grundfos</strong> E-<strong>pumps</strong> are fitted with a fieldbus<br />

interface based on the RS-485 hardware platform.<br />

The bus is named GENIbus (<strong>Grundfos</strong> Electronics<br />

Network Intercommunication) and is a <strong>Grundfos</strong>developed<br />

bus with its own protocol. The GENIbus<br />

was first introduced in 1991 when <strong>Grundfos</strong> introduced<br />

the first <strong>pumps</strong> with integrated variable frequency drive<br />

and controller to the market.<br />

Bus communication between E-<strong>pumps</strong> and other<br />

equipment like building management systems<br />

(SCADA) can take place with a <strong>Grundfos</strong> gateway and<br />

a standardized fieldbus, for instance Profibus.<br />

CIU<br />

CIM<br />

Communication to other equipment via<br />

a <strong>Grundfos</strong> gateway<br />

E-<strong>pumps</strong> can communicate with building management<br />

systems (SCADA) via a CIU unit which converts from<br />

the GENIbus to another fieldbus, such as LON,<br />

Profibus, Modbus, etc.<br />

CIU unit<br />

The <strong>Grundfos</strong> CIU unit (Communication Interface Unit)<br />

is used as a gateway for communication between<br />

E-<strong>pumps</strong> and other buses than GENIbus.<br />

The CIU unit is to be mounted on the wall or in a<br />

cabinet. It contains a CIM module (Communication<br />

Interface Module) for a specific bus.<br />

The CIU unit has no functionality in itself, but must<br />

have a CIM module fitted to be able to communicate.<br />

The CIU unit must be used for MLE motors, 10 Hp and<br />

below. The CIM module can be fitted directly in the<br />

MLE motor terminal box (15 - 30 Hp only).<br />

Communication<br />

The CIU unit can communicate the following data<br />

points between the E-<strong>pumps</strong> and the management<br />

system:<br />

CIU unit<br />

Bus communication<br />

Only 15 - 30 Hp<br />

<strong>pumps</strong><br />

Fig. 64 Bus communication for E-<strong>pumps</strong><br />

TM05 2979 0812<br />

Data points<br />

Multistage<br />

E-<strong>pumps</strong> with or<br />

without sensor<br />

TP<br />

Series 1000<br />

without<br />

sensor<br />

TPE<br />

Series<br />

2000<br />

From management system (SCADA) to E-pump<br />

Control mode ● 1) ● 1) ● 2)<br />

Setpoint, 0-100 % ● ● ●<br />

Start/stop ● ● ●<br />

Max. ● ● ●<br />

Min. ● ● ●<br />

From E-pump to management system (SCADA)<br />

Fault indication ● ● ●<br />

Operating indication ● ● ●<br />

Actual control mode ● ● ●<br />

Actual head ● 3) ● 3) ●<br />

Actual power consumption<br />

● ● ●<br />

Operating hours ● ● ●<br />

Energy consumption ● ● ●<br />

Liquid temperature ● ● ●<br />

Speed [rpm] ● ● ●<br />

● Available.<br />

1) Control modes: Controlled or uncontrolled.<br />

2)<br />

Control modes: Proportional pressure, constant pressure or<br />

constant curve.<br />

3) Actual controlled value, depending on sensor type.<br />