FAULT FINDING<br />

90 H.....1..... (CONTROL T<strong>HE</strong>RMISTOR [FLOW] ERROR)<br />

Remove the boiler <strong>co</strong>ntrol thermistor from the CH<br />

flow pipe and dis<strong>co</strong>nnect thermistor wires.<br />

Check resistance using a suitable multimeter<br />

<strong>co</strong>nnected across the thermistor’s terminal pins<br />

At 25 o C expect 9,700 - 10,<strong>30</strong>0 Ohms<br />

At 60 o C expect 2,400 - 2,600 Ohms<br />

At 85 o C expect 1,000 - 1,100 Ohms<br />

Are the thermistor values <strong>co</strong>rrect ?<br />

YES<br />

Is there <strong>co</strong>ntinuity between the PCB and the thermistor ?<br />

91 H.....2..... (CONTROL T<strong>HE</strong>RMISTOR [RETURN] ERROR)<br />

Remove the boiler return thermistor from the CH return pipe.<br />

Check resistance using a suitable multimeter<br />

<strong>co</strong>nnected across the thermistor’s terminal pins<br />

At 25 o C expect 9,700 - 10,<strong>30</strong>0 Ohms<br />

At 60 o C expect 2,400 - 2,600 Ohms<br />

At 85 o C expect 1,000 - 1,100 Ohms<br />

Are the thermistor values <strong>co</strong>rrect ?<br />

YES<br />

Is there <strong>co</strong>ntinuity between the PCB and the thermistor ?<br />

92 H.....3..... (DHW T<strong>HE</strong>RMISTOR ERROR)<br />

Remove the boiler DHW thermistor from the plate<br />

heat exchanger and dis<strong>co</strong>nnect thermistor wires.<br />

Check resistance using a suitable multimeter<br />

<strong>co</strong>nnected across the thermistor’s terminal pins<br />

At 25 o C expect 9,700 - 10,<strong>30</strong>0 Ohms<br />

At 60 o C expect 2,400 - 2,600 Ohms<br />

At 85 o C expect 1,000 - 1,100 Ohms<br />

Are the thermistor values <strong>co</strong>rrect ?<br />

YES<br />

Is there <strong>co</strong>ntinuity between the PCB and the thermistor ?<br />

NO<br />

YES<br />

NO<br />

NO<br />

YES<br />

NO<br />

NO<br />

YES<br />

NO<br />

Replace the thermistor<br />

Replace PCB<br />

Check and replace wiring as necessary<br />

Replace the thermistor<br />

Replace PCB<br />

Check and replace wiring as necessary<br />

Replace the thermistor<br />

Replace PCB<br />

Check and replace wiring as necessary<br />

FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING<br />