BENCHMARK No.<br />
COLLECTIVE MARK<br />
GAS BOILER COMMISSIONING C<strong>HE</strong>CKLIST<br />
BOILER SERIAL No.<br />
NOTIFICATION No.<br />
CONTROLS To <strong>co</strong>mply with the Building Regulations, each section must have a tick in one or other of the boxes<br />
TIME & TEMPERATURE CONTROL TO <strong>HE</strong>ATING ROOM T/STAT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT<br />
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER COMBI BOILER<br />
<strong>HE</strong>ATING ZONE VALVES FITTED NOT REQUIRED<br />
HOT WATER ZONE VALVES FITTED NOT REQUIRED<br />
T<strong>HE</strong>RMOSTATIC RADIATOR VALVES<br />
FITTED<br />
AUTOMATIC BYPASS TO SYSTEM FITTED NOT REQUIRED<br />
FOR ALL BOILERS CONFIRM T<strong>HE</strong> FOLLOWING<br />
T<strong>HE</strong> SYSTEM HAS BEEN FLUS<strong>HE</strong>D IN ACCORDANCE WITH T<strong>HE</strong> BOILER MANUFACTURERÕS INSTRUCTIONS?<br />
T<strong>HE</strong> SYSTEM CLEANER USED<br />
T<strong>HE</strong> INHIBITOR USED<br />
FOR T<strong>HE</strong> CENTRAL <strong>HE</strong>ATING MODE, MEASURE & RECORD<br />
GAS RATE<br />
BURNER OPERATING PRESSURE (IF APPLICABLE)<br />
CENTRAL <strong>HE</strong>ATING FLOW TEMPERATURE<br />
CENTRAL <strong>HE</strong>ATING RETURN TEMPERATURE<br />
FOR COMBINATION BOILERS ONLY<br />
m 3 /hr<br />
N/A<br />
ft 3 /hr<br />
mbar<br />
o<br />
C<br />
o<br />
C<br />
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO<br />
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?<br />
FOR T<strong>HE</strong> DOMESTIC HOT WATER MODE, MEASURE & RECORD<br />
GAS RATE<br />
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)<br />
COLD WATER INLET TEMPERATURE<br />
HOT WATER OUTLET TEMPERATURE<br />
WATER FLOW RATE<br />
FOR CONDENSING BOILERS ONLY CONFIRM T<strong>HE</strong> FOLLOWING<br />
T<strong>HE</strong> CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH<br />
T<strong>HE</strong> MANUFACTURER'S INSTRUCTIONS?<br />
FOR ALL INSTALLATIONS CONFIRM T<strong>HE</strong> FOLLOWING<br />
m 3 /hr<br />
N/A<br />
ft 3 /hr<br />
mbar<br />
o<br />
C<br />
o<br />
C<br />
lts/min<br />
YES<br />
T<strong>HE</strong> <strong>HE</strong>ATING AND HOT WATER SYSTEM COMPLIES<br />
WITH CURRENT BUILDING REGULATIONS<br />
T<strong>HE</strong> APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED<br />
IN ACCORDANCE WITH T<strong>HE</strong> MANUFACTURER'S INSTRUCTIONS<br />
IF REQUIRED BY T<strong>HE</strong> MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A YES CO/CO2 RATIO<br />
T<strong>HE</strong> OPERATION OF T<strong>HE</strong> APPLIANCE AND SYSTEM<br />
CONTROLS HAVE BEEN DEMONSTRATED TO T<strong>HE</strong> CUSTOMER<br />
T<strong>HE</strong> MANUFACTURER'S LITERATURE HAS BEEN LEFT WITH T<strong>HE</strong> CUSTOMER<br />
COMMISSIONING ENG'S NAME PRINT<br />
SIGN<br />
CORGI ID No.<br />
DATE