VALIDATING TAGS<br />

CRIMSON USER MANUAL - MODULAR CONTROLLER<br />

VALIDATING TAGS<br />

Selecting the Tags icon in the left-hand pane of the Tags window will allow access to the<br />

Validate All Tags button. Pressing this button will recompile all expressions in your database,<br />

fixing any broken communications references and updating tag reference counts. You should<br />

not need to push this button unless you have removed and then replaced tags, and wish to<br />

repair the expression that will have been broken when the tags were deleted.<br />

EXPORTING TAG MAPPINGS<br />

Selecting the Tags icon in the left-hand pane of the Tags window will also allow access to the<br />

tag import and export facilities. The Export to File button can be used to export the tag names<br />

and mappings to a CSV file for subsequent editing in Microsoft Excel or some other suitable<br />

tool. The Import from File button can then be used to re-import the file, changing the tag<br />

mappings in line with the changes made to the file. These facilities are useful when porting an<br />

application from one PLC to another, as it allows all the mappings to be changed in a single<br />

operation. The import facility can also be used to create tags to correspond to data mappings<br />

that have been exported into a CSV file from a Red Lion Modular Controller.<br />

LOGGING EVENT MESSAGES *<br />

When the Tags icon is selected in the left-hand pane, the right-hand pane of the Tags window<br />

contains options to control the logging of the messages generated by the alarms and events<br />

attached to each tag…<br />

• The Send to Raw Port property is used to indicate which communications port<br />

events should be printed to. The port in question must have a raw port driver<br />

bound to it as described in the Using Raw Ports chapter. Note that a serial driver<br />

or a TCP/IP driver may be used as required by the application.<br />

• The Save to CompactFlash property is used to enable the writing of events to<br />

CSV files on the card fitted to the Master. Events are stored using techniques<br />

similar to those for data logging. The New File Every and Retain at Most<br />

properties control how files are allocated. Refer to the Configuring Data Logging<br />

chapter for information on how the data is written and how files are named.<br />

NOTES FOR EDICT USERS<br />

Users of Red Lion’s Edict-97 software should note…<br />

• Crimson’s Data Tags window is used to perform all of the various functions that<br />

were previously implemented using the Named Data window, the Alarm<br />

Scanner, and the Trigger Table.<br />

* Not present on monochrome virtual HMI.<br />

PAGE 130<br />

http://www.redlion.net/controller