CSSG – STRAIN GAGE INPUT PID MODULE PROGRAMMING<br />

CRIMSON USER MANUAL - MODULAR CONTROLLER<br />

required output to reach and maintain setpoint, and acts accordingly. In manual<br />

mode, the output can be controlled directly by writing to the power variable.<br />

• The Initial Setpoint property is used as the setpoint value upon initialization.<br />

• Manual Power is the level the PID module will assume in manual mode. Values<br />

in excess of 100% and –100% can be entered to overcome the limitations caused<br />

by Power Transfer values, such as gains and offsets that would otherwise limit<br />

the outputs to less than their maximums.<br />

• The Download Scaling property determines which scaling values, if any, will be<br />

downloaded to the module. To avoid overwriting the scaling values of a<br />

calibrated process, set this value to No.<br />

SMARTONOFF<br />

SmartOnOff is designed for situations where on-off control would normally be used, but<br />

where the advantages of PID are also desired. When the reverse or direct output is placed into<br />

this mode, the control output will either be driven on or off, with no intermediate values or<br />

time proportioning. However, rather than use the process value to decide when to turn the<br />

output on, SmartOnOff looks at the output of the PID calculation and activates the output<br />

when it exceeds half the defined gain for that channel. For example, with default settings,<br />

SmartOnOff for the reverse output would turn the output on once the PID algorithm called for<br />

50% power or more, with the hysteresis value being used to ensure that small changes in the<br />

PID calculation do not produce relay chatter.<br />

• The Hysteresis property is used to eliminate output chatter by separating the on<br />

and off points of the output(s) when performing SmartOnOff control. The<br />

Hysteresis value is centered around the setpoint, that is, the transition points of<br />

the output will be offset above and below the setpoint by half of the Hysteresis<br />

value.<br />

THE CONTROL TAB<br />

PAGE 36<br />