CONFIGURING DATA LOGGING<br />

NOTES FOR EDICT USERS<br />

• -num can be used to override the phone number for the connection.<br />

EXAMPLE USAGE<br />

As an example, the following command line…<br />

websync –poll 10 –path C:\Logs 192.9.200.52<br />

…will read the log files for all data logs on the Master with the IP address of 192.9.200.52,<br />

and will store these logs under subdirectories of the C:\Logs directory. WebSync will<br />

continue to execute, and will repeat the polling process every ten minutes. The polling<br />

interval must obviously be set such that it is much less than the sampling rate times the<br />

number of samples in a file times the number of log files to be retained. If this constraint is<br />

met, the directory on the PC will accumulate copies of all the log files from the Master.<br />

NOTES FOR EDICT USERS<br />

Users of Red Lion’s Edict-97 software should note…<br />

• Logs within Crimson record the time and date of each sample, and do not need to<br />

store the “empty” values used by Edict to mark power-down periods. When a<br />

Master module is powered-down, this will show simply as a gap in the log files.<br />