MODULE CONFIGURATION<br />

CSPID – PID MODULE PROGRAMMING<br />

OUTPUTS/CYCLE TIMES<br />

DATA DESCRIPTION RANGE ACCESS<br />

CycleTime1 Cycle Time for Output 1 0.1 – 60.0 sec R/W<br />

CycleTime2 Cycle Time for Output 2 0.1 – 60.0 sec R/W<br />

CycleTime3 Cycle Time for Output 3 0.1 – 60.0 sec R/W<br />

CycleTime4 Cycle Time for Output 4 (CSPID2 only) 0.1 – 60.0 sec R/W<br />

OUTPUTS/REMOTE DATA<br />

DATA DESCRIPTION RANGE ACCESS<br />

DigRemote1<br />

Digital Remote 1 – Outputs assigned to Digital Remote<br />

can be controlled by writing the DigRemote bit to a 1 or 0.<br />

0 or 1 (bit) R/W<br />

DigRemote2 Digital Remote 2 – See DigRemote1 0 or 1 (bit) R/W<br />

DigRemote3 Digital Remote 3 – See DigRemote1 0 or 1 (bit) R/W<br />

DigRemote4 Digital Remote 4 – See DigRemote1 0 or 1 (bit) R/W<br />

AnlRemote1<br />

Analog Remote Value 1 – Outputs assigned to Analog<br />

Remote can be controlled by writing a number to this<br />

word.<br />

* R/W<br />

AnlRemote2 Analog Remote Value 2 – See AnlRemote1 * R/W<br />

AnlRemote3 Analog Remote Value 3 – See AnlRemote1 * R/W<br />

AnlRemote4 Analog Remote Value 4 – See AnlRemote1 * R/W<br />

OUTPUTS/INFORMATION<br />

DATA DESCRIPTION RANGE ACCESS<br />

OP1State State of Output 1 0 or 1 (bit) R<br />

OP2State State of Output 2 0 or 1 (bit) R<br />

OP3State State of Output 3 0 or 1 (bit) R<br />

* Configuration dependent. Except for the application detailed below, these numbers may be<br />

treated as signed integers. All temperature inputs are measured to a tenth of a degree<br />

resolution. For process inputs, the resolution is dependent on the user scaling values.<br />

Application exception: If the application involves Fahrenheit measurement over 3000 degrees<br />

with a C type thermocouple, the following values should be treated as unsigned – PV, ReqSP,<br />

ActSP and AlarmData 1-4 (when configured for absolute operation).<br />

REVISION 6 PAGE 33