MODULE CONFIGURATION<br />

CSPID – PID MODULE PROGRAMMING<br />

LINEAR OUTPUT - (CSPID1 ONLY)<br />

• The Output Type property is used to select between 0-10 V, 0-20 mA, or 4-20<br />

mA outputs. Make sure that the output jumpers, located on the side of the<br />

module, are set for the same output type.<br />

• The Mapping property is used to assign the module’s analog output to one of<br />

various internal properties or values eg. the Mapping property should be set to<br />

Heat Power to control a heat-only process via the analog output.<br />

• The Drive Min At and Drive Max At values are used to scale the analog output.<br />

The units expressed are the same as those of the Mapping value, so the<br />

numerical limits vary eg. values of 0% and 100% are typically used to control a<br />

valve’s position in heat-only applications.<br />

• The Output Filter is a time constant entered in seconds that dampens the<br />

response of the analog output. Increasing the value increases the dampening.<br />

• The Output Deadband value can be used to prevent the analog output from<br />

changing when only small adjustments are called for. This is useful in preventing<br />

mechanical wear when driving a linear input valve. The analog output will not<br />

adjust unless the change called for exceeds half of the deadband value. i.e. With<br />

a deadband of 10 %, and an output value of 50 %, the output will not change<br />

until 45 % or 55 % is called for. The units expressed are the same as those of the<br />

Mapping value.<br />

• The Output Update time can be used to decrease the update frequency of the<br />

analog output. When the Output Update timer expires, the analog output checks<br />

to see if the required change is greater than the Output Deadband value. If the<br />

required change is greater, the output will reflect the new value. If not, the output<br />

does not change, and the timer starts again.<br />

AUTO-TUNING<br />

OVERVIEW<br />

Auto-tune may be used to establish the optimal P, I, D, and Power Filter values. By cycling<br />

the process through four on/off cycles, the module learns information about the process, and<br />

determines the best values.<br />