CSSG – STRAIN GAGE INPUT PID MODULE PROGRAMMING<br />

CRIMSON USER MANUAL - MODULAR CONTROLLER<br />

THE ALARMS TAB<br />

The four “soft” process alarms may be used to monitor process status, and may be used to<br />

actuate the module’s physical outputs. Otherwise, the bit alone may be monitored via the<br />

system itself, or via external devices.<br />

• The Mode property determines what behavior the alarm will assume. The table<br />

below describes the various selections.<br />

MODE<br />

Absolute Low<br />

Absolute High<br />

Deviation Low<br />

Deviation High<br />

In Band<br />

Out of Band<br />

DESCRIPTION<br />

The alarm activates when the measured value falls below<br />

the Alarm Value. The alarm deactivates when the<br />

measured value goes above the Alarm Value + Hysteresis.<br />

The alarm activates when the measured value exceeds the<br />

Alarm Value. The alarm deactivates when the measured<br />

value falls below the Alarm Value – Hysteresis.<br />

If the measured value falls below the Setpoint Value by<br />

the amount of the Alarm Value, the alarm activates. In<br />

this mode, the alarm point tracks the Setpoint Value.<br />

If the measured value exceeds the Setpoint Value by the<br />

amount of the Alarm Value, the alarm activates. In this<br />

mode, the alarm point tracks the Setpoint Value.<br />

If the difference between the Setpoint Value and the<br />

measured value is not greater than the Alarm Value, the<br />

alarm activates.<br />

If the measured value exceeds, or falls below, the Setpoint<br />

Value by an amount equal to the Alarm Value, the alarm<br />

activates. In this mode, the alarm point tracks the Setpoint<br />

Value.<br />

• The Assignment property changes the value that the alarms will monitor, and<br />

therefore react to.<br />

PAGE 40<br />

http://www.redlion.net/controller