MODULE CONFIGURATION<br />

CSOUT – ANALOG OUTPUT MODULE PROGRAMMING<br />

THE INITIAL OUTPUT TAB<br />

INITIALIZATION<br />

• The initialization parameters provide initial output values, which are normally<br />

controlled by a PC or PLC. In typical applications, these settings will only be<br />

used until communications is established for the first time.<br />

• The Include in Download property is used to determine whether the initialization<br />

values will be downloaded to the module. Selecting “no” allows modification<br />

and download of databases at will, without accidentally overwriting the output<br />

values.<br />

• The Data 1 to Data 4 properties are the initial output values used for Output 1 to<br />

Output 4, respectively. These values are scaled as per the Data Low, Data High,<br />

Output Low and Output High properties.<br />

OUTPUT ACTION<br />

The output will "rail" at the Output Low and Output High values. i.e. If a Data value that is<br />

less than the Data Low value is written to the module, the output will remain at Output Low,<br />

and the alarm will turn on. Conversely, if a Data value that is greater than Data High value is<br />

written to the module, the output will remain at Output High, and the alarm will turn on.<br />

REVISION 6 PAGE 57