CSSG – STRAIN GAGE INPUT PID MODULE PROGRAMMING<br />

CRIMSON USER MANUAL - MODULAR CONTROLLER<br />

Proportional Band is adjustable from 0.0% to 1000.0%, and should be set to a<br />

value that provides the best response to a process disturbance while minimizing<br />

overshoot. A Proportional Band of 0.0% forces the controller into On/Off<br />

Control with its characteristic cycling at setpoint. The optimal value may be<br />

established by invoking Auto-tune.<br />

• The Integral Time is the time in seconds that it takes the integral action to equal<br />

the proportional action, during a constant process error. As long as the error<br />

exists, integral action is repeated each Integral Time. The higher the value, the<br />

slower the response. The optimal value may be established by invoking autotune.<br />

The Integral Time is adjustable from 0 to 6000.0 seconds.<br />

• The Derivative Time is the seconds per repeat that the controller looks ahead at<br />

the ramping error to see what the proportional contribution will be and it<br />

matches that value every Derivative Time. As long as the ramping error exists,<br />

the derivative contribution is repeated every derivative time. Increasing the value<br />

helps to stabilize the response, but too high of a value, coupled with noisy signal<br />

processes, may cause the output to fluctuate too greatly, yielding poor control.<br />

Setting the time to zero disables derivative action. The optimal Derivative Time<br />

may be established by invoking auto-tune. The value is adjustable from 0 to<br />

600.0 seconds.<br />

• The Power Filter is a time constant, entered in seconds, that dampens the<br />

calculated output power. Increasing the value increases the dampening effect.<br />

Generally, a Power Filter in the range of one-twentieth to one-fiftieth of the<br />

controller’s integral time (or process time constant) is effective. Values longer<br />

than these may cause controller instability due to the added lag effect.<br />

THE POWER TAB<br />

POWER TRANSFER<br />

• The Output Offset value effectively shifts the zero output point of the module’s<br />

output power calculation. This feature is most commonly used in proportionalonly<br />

applications, to remove steady-state error.<br />

PAGE 38<br />

http://www.redlion.net/controller