BD2 System — 160 ... 1250 A<br />

© <strong>Siemens</strong> AG <strong>2011</strong><br />

Introduction<br />

■ Design<br />

Trunking units<br />

Power is transferred through nickel-plated and tinned aluminum<br />

busbars as well as tinned copper busbars.<br />

The low inherent impedance and large surface area of the busbars<br />

limit the heat build-up.<br />

The result is a low transmission loss and a low voltage drop.<br />

Enclosures<br />

The enclosure is made of hot galvanized steel with a paint finish.<br />

Color: RAL <strong>70</strong>35 (light gray).<br />

Protected to IP52 degree of protection as standard. This can be<br />

increased to IP54 or IP55 with additional parts.<br />

N L1 L2 L3 ½PE<br />

167<br />

160 ... 400 A<br />

68<br />

BD2A-2, BD2C-2 trunking units<br />

NSV0_00084a<br />

N L1 L2 L3 ½PE<br />

167<br />

630 ... 1250 A<br />

N L1 L2 L3 PE<br />

126<br />

Connections<br />

Trunking units are connected quickly and securely via the joint<br />

block.<br />

NSV0_00090<br />

Left: Flange cover<br />

Right: Joint blocks<br />

Joint blocks<br />

Features:<br />

• Even holding pressure ensures completely secure connection<br />

of all five busbars. Fast mounting up to 400 A with plug-in terminal,<br />

from 630 A to 1250 A with single-bolt type terminal.<br />

• The built-in expansion compensation absorbs the heat expansion<br />

of the busbars.<br />

• The terminal can be tightened using conventional tools.<br />

• Two sizes are available for the whole system.<br />

• The joint block is supplied as an integral part of the trunking<br />

units and junction units.<br />

N L1 L2 L3 PE<br />

167<br />

160 ... 400 A<br />

68<br />

NSV0_00086a<br />

167<br />

630 ... 1250 A<br />

126<br />

NSV0_00092<br />

5<br />

BD2A-3, BD2C-3 trunking units,<br />

BD2A-..., BD2C-... junction units, feeder units<br />

Tap-off points<br />

The busbar support and tap-off point form a unit.<br />

The leading/delayed PE contact at the tap-off unit provides<br />

positive opening or closing of the tap-off point.<br />

The tap-off point can be coded at the factory on request,<br />

together with the tap-off unit. The tap-off point is sealable.<br />

BD2-AK1, BD2-AK2(3), BD2-AK02(03) and BD2-AK04 tap-off<br />

units are plug-in types for all systems, BD2-AK05(06) tap-off<br />

units are only for systems from 630 A.<br />

Left: BD2-400-SK for 160 to 400 A<br />

Right: BD2-1250-EK for 630 to 1250 A<br />

Four screws provide the mechanical connection to the enclosure.<br />

NSV0_00094<br />

NSV0_00088<br />

Left: Tap-off point for BD2.-160 to BD2.-400<br />

Right: Tap-off point for BD2.-630 to BD2.-1250<br />

5/4 <strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong>