© <strong>Siemens</strong> AG <strong>2011</strong><br />

BD2 System — 160 ... 1250 A<br />

Tap-off units for international use<br />

DT Type Order No. Version<br />

Circuit breaker/ Rated current Rated<br />

Weight<br />

voltage U e approx.<br />

setting range I n<br />

operational<br />

PS*/<br />

P. unit per unit<br />

A A V kg<br />

Sheet-steel enclosures, size 04, 05 and 06, up to 530 A<br />

With circuit breaker,<br />

normal switching capacity,<br />

with rotary operating mechanism,<br />

bolt terminals<br />

• With thermal-magnetic trip unit 3-pole<br />

3VL27 16<br />

160 400 X BD2-AK04/ BVP:610424 1 unit 30.000<br />

125... 160<br />

LSD-DC160-N<br />

3VL37 20<br />

200 400 X BD2-AK04/ BVP:610430 1 unit 30.000<br />

160 ... 200<br />

LSD-DC200-N<br />

3VL37 25<br />

250 400 X BD2-AK04/ BVP:610436 1 unit 30.000<br />

200 ... 250<br />

LSD-DC250-N<br />

3VL47 40<br />

400 400 X BD2-AK05/ BVP:610442 1 unit 35.000<br />

320 ... 400<br />

LSD-DC400-N<br />

3VL57 63<br />

530 400 X BD2-AK06/ BVP:610448 1 unit 40.000<br />

NSV0_01011<br />

500 ... 530<br />

LSD-DC630-N<br />

• With solid-state trip unit, selective 3-pole<br />

3VL27 16<br />

160 400 X BD2-AK04/ BVP:610428 1 unit 30.000<br />

64 ... 160<br />

LSD-AE160-N<br />

3VL37 20<br />

200 400 X BD2-AK04/ BVP:610434 1 unit 30.000<br />

80 ... 200<br />

LSD-AE200-N<br />

3VL37 25<br />

250 400 X BD2-AK04/ BVP:610440 1 unit 30.000<br />

100 ... 250<br />

LSD-AE250-N<br />

3VL47 40<br />

400 400 X BD2-AK05/ BVP:610446 1 unit 35.000<br />

160 ... 400<br />

LSD-AE400-N<br />

3VL57 63<br />

530 400 X BD2-AK06/ BVP:610452 1 unit 40.000<br />

NSV0_01011<br />

252 ... 530<br />

LSD-AE630-N<br />

• With thermal-magnetic trip unit,<br />

selective (N release 60 %)<br />

NSV0_01011<br />

4-pole<br />

3VL27 16<br />

125 ... 160<br />

3VL37 20<br />

160 ... 200<br />

3VL37 25<br />

200 ... 250<br />

3VL47 40<br />

320 ... 400<br />

3VL57 63<br />

500 ... 530<br />

160 400 X BD2-AK04/<br />

LSD-EC160-N<br />

200 400 X BD2-AK04/<br />

LSD-EC200-N<br />

250 400 X BD2-AK04/<br />

LSD-EC250-N<br />

400 400 X BD2-AK05/<br />

LSD-EC400-N<br />

530 400 X BD2-AK06/<br />

LSD-EC630-N<br />

BVP:610426 1 unit 30.000<br />

BVP:610432 1 unit 30.000<br />

BVP:610438 1 unit 30.000<br />

BVP:610444 1 unit 35.000<br />

BVP:610450 1 unit 40.000<br />

Special colors available on request.<br />

Use plastic cable glands with strain relief (not included in scope<br />

of supply).<br />

For BD2-AK04, -AK05 and -AK06, the KT3 or KT4 cable grommet<br />

is included in scope of supply.<br />

The tap-off units, size 05 and 06, are suitable only for systems<br />

630 A to 1250 A.<br />

5<br />

* You can order this quantity or a multiple thereof.<br />

<strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong><br />