CD-K System — 25 ... 40 A<br />
© <strong>Siemens</strong> AG <strong>2011</strong><br />
Introduction<br />
End flanges<br />
Different phase pick-offs can be achieved by simply repositioning<br />
the contacts.<br />
NSV0_00004<br />
L3<br />
L2<br />
L1<br />
N<br />
PE<br />
These flanges provide touch protection against direct contact at<br />
the ends of the busbar line. They fit all systems.<br />
Feeder units<br />
NSV0_00007<br />
L1 + N + PE L2 + N + PE L3 + N + PE<br />
3<br />
Two versions are available:<br />
• as entry feeder unit for 2 × 25 A, 30 A, 40 A and 2 × 40 A,<br />
• as end feeder unit for 2 × 25 A, 30 A, 40 A and 2 × 40 A.<br />
The scope of supply also includes 1 end flange for each respectively.<br />
Cable entry from 3 sides; use cable gland made of plastic,<br />
metric, with strain relief M25 or M32 (not included in the scope<br />
of supply).<br />
Tap-off plugs<br />
Insulated tap-off plugs are used for taking current from the<br />
tap-off points on the trunking units. They can be mounted and<br />
removed by hand. This is even possible with live busbars.<br />
The following are available:<br />
• 3-pole and 5-pole versions without fuse base, with halogenfree,<br />
flame-retardant cable.<br />
• 3-pole and 5-pole versions without fuse base, with terminal<br />
and M20 plastic cable grommets.<br />
• 3-pole versions with fuse base for cylindrical fuses<br />
8.5 mm × 31.5 mm; type gG (IEC) and type gL (VDE) quick,<br />
with halogen-free, flame-retardant cable.<br />
• 3-pole and 5-pole versions with fuse bases for 1 or 3 cylindrical<br />
fuses 8.5 mm × 31.5 mm; type gG (IEC) and type gL<br />
(VDE) quick, with terminal and M20 plastic cable grommets.<br />
NSV0_00005<br />
The phase pick-off is factory set for 5-pole tap-off plugs.<br />
The phase assignment of the tap-off plugs is visible from the outside.<br />
Cables of up to 2.5 mm 2 can be connected to tap-off plugs with<br />
terminals. The connecting cables should be supported separately<br />
if necessary.<br />
L3<br />
L1<br />
L2<br />
NSV0_00036<br />
NSV0_00010<br />
N<br />
NSV0_00037<br />
L2 L3<br />
L1<br />
N<br />
NSV0_00009<br />
On the 3-pole tap-off plugs, the phase pick-off can be changed,<br />
i. e. repositioned (L1, L2 or L3 can be selected).<br />
3/4 <strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong>