08.11.2014 Views

Catalog LV 70 2011 - Low & Medium Voltage - Siemens

Catalog LV 70 2011 - Low & Medium Voltage - Siemens

Catalog LV 70 2011 - Low & Medium Voltage - Siemens

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

CD-K System — 25 ... 40 A<br />

© <strong>Siemens</strong> AG <strong>2011</strong><br />

Introduction<br />

End flanges<br />

Different phase pick-offs can be achieved by simply repositioning<br />

the contacts.<br />

NSV0_00004<br />

L3<br />

L2<br />

L1<br />

N<br />

PE<br />

These flanges provide touch protection against direct contact at<br />

the ends of the busbar line. They fit all systems.<br />

Feeder units<br />

NSV0_00007<br />

L1 + N + PE L2 + N + PE L3 + N + PE<br />

3<br />

Two versions are available:<br />

• as entry feeder unit for 2 × 25 A, 30 A, 40 A and 2 × 40 A,<br />

• as end feeder unit for 2 × 25 A, 30 A, 40 A and 2 × 40 A.<br />

The scope of supply also includes 1 end flange for each respectively.<br />

Cable entry from 3 sides; use cable gland made of plastic,<br />

metric, with strain relief M25 or M32 (not included in the scope<br />

of supply).<br />

Tap-off plugs<br />

Insulated tap-off plugs are used for taking current from the<br />

tap-off points on the trunking units. They can be mounted and<br />

removed by hand. This is even possible with live busbars.<br />

The following are available:<br />

• 3-pole and 5-pole versions without fuse base, with halogenfree,<br />

flame-retardant cable.<br />

• 3-pole and 5-pole versions without fuse base, with terminal<br />

and M20 plastic cable grommets.<br />

• 3-pole versions with fuse base for cylindrical fuses<br />

8.5 mm × 31.5 mm; type gG (IEC) and type gL (VDE) quick,<br />

with halogen-free, flame-retardant cable.<br />

• 3-pole and 5-pole versions with fuse bases for 1 or 3 cylindrical<br />

fuses 8.5 mm × 31.5 mm; type gG (IEC) and type gL<br />

(VDE) quick, with terminal and M20 plastic cable grommets.<br />

NSV0_00005<br />

The phase pick-off is factory set for 5-pole tap-off plugs.<br />

The phase assignment of the tap-off plugs is visible from the outside.<br />

Cables of up to 2.5 mm 2 can be connected to tap-off plugs with<br />

terminals. The connecting cables should be supported separately<br />

if necessary.<br />

L3<br />

L1<br />

L2<br />

NSV0_00036<br />

NSV0_00010<br />

N<br />

NSV0_00037<br />

L2 L3<br />

L1<br />

N<br />

NSV0_00009<br />

On the 3-pole tap-off plugs, the phase pick-off can be changed,<br />

i. e. repositioned (L1, L2 or L3 can be selected).<br />

3/4 <strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!