BD2 System — 160 ... 1250 A<br />
Introduction<br />
Feeder units<br />
For the incoming supply to BD2 runs, various feeder unit versions<br />
are available to meet different requirements.<br />
If using end feeder units in addition to a middle infeed, an additional<br />
terminal block is required for each end feeder unit.<br />
NSV0_00117<br />
Example: end feeder unit with connected cabling box<br />
Features:<br />
• Cables are introduced from the front face.<br />
• Cable entry plate (aluminum) for single-core cable entry.<br />
• Cable connection is via bolts. The bolts are included in scope<br />
of supply.<br />
• The factory-fitted jumper between PE and N can be removed<br />
for connection of five-core cables.<br />
• Feeder units are supplied without joint block.<br />
• They are not directly mountable on junction units.<br />
For double-ended infeed, an additional joint block is required.<br />
BD2.-...-EE end feeder unit and BD2.-...-ME center feeder unit<br />
End feeder units<br />
Cable entry is from the front; cable entry from the side is possible<br />
for the version with a BD2.-...-EE-KR cabling box.<br />
NSV0_00120<br />
BD2.-...-EE and BD2.-...-EE-KR end feeder units<br />
The phase sequence can be changed on site by rotating the<br />
busbar pack.<br />
NSV0_00122<br />
BD2.-...-EE double-end feeder unit<br />
To distribute large amounts of power with small busbar crosssections,<br />
it is sensible to use a center feeder unit in some cases.<br />
It is mounted in the middle of a busbar line between two trunking<br />
units. The left run and the right run are supplied simultaneously<br />
with one supply cable. If using a 1000 A middle infeed, it is therefore<br />
possible to infeed 2000 A. In this case, special consideration<br />
must be given to the overload and short-circuit protection<br />
of the busbar system.<br />
If the short-circuit protection is not assured by the upstream protective<br />
device and/or the overload is not due to the type and<br />
number of loads, additional protective measures are required.<br />
Two options are possible:<br />
• Use of a center feeder unit with one coupling unit on the right<br />
and left respectively next to the feeder unit. The coupling unit<br />
must be equipped with a protective device (fuse or circuit<br />
breaker) that ensures the short-circuit and overload function.<br />
• Use of two end feeder units that are arranged centrally in the<br />
busbar line. The two supply cables are separately fused in the<br />
distribution system.<br />
End feeder units with switch disconnector<br />
End feeder units with switch disconnector<br />
NSV0_01475<br />
5<br />
<strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong><br />
5/7