BD2 System — 160 ... 1250 A<br />
Max. length/height of vertical BD2 busbar lines,<br />
supported by one BD2-BWV or BD2-BDV retaining element<br />
BD2A-.-...<br />
Rated current A 160 250 400 630 800 1000 1250<br />
Max. supported length or height<br />
m 11.3 10.9 7.9 5.8 5.8 5.3 –<br />
at max. load (see below)<br />
Max. weight per 3.25 m trunking unit<br />
fitted with tap-off units<br />
kg 50 53 74 106 108 108 –<br />
Configuration information<br />
BD2C-.-...<br />
Rated current A 160 250 400 630 800 1000 1250<br />
Max. supported length or height<br />
m 10.0 9.9 7.2 5.2 4.8 4.1 3.25<br />
at max. load (see below)<br />
Max. weight per 3.25 m trunking unit<br />
fitted with tap-off units<br />
kg 50 53 74 106 108 108 108<br />
Notes<br />
For taller BD2 busbar lines, additional mountings must be used.<br />
■ Function<br />
The maximum load applied to the BD2-BWV and BD2-BDV vertical<br />
retaining elements must not exceed 175 kg. They must be<br />
fitted in the area of the terminal.<br />
Overload and short-circuit protection<br />
Busbar trunking systems need to be protected against short-circuits<br />
and overloads. Fuses and circuit breakers are available for<br />
use as protective devices. With the selection of this protection<br />
equipment the level of the expected short-circuit currents, selectivity<br />
requirements or operating and signaling functions are also<br />
factors for consideration.<br />
If circuit-breakers are used, the thermally delayed overload release<br />
is set to the rated current value for the busbar trunking system.<br />
This means that the busbar trunking system can be 100 %<br />
loaded.<br />
When you decide on your short-circuit protection via fuses and<br />
circuit-breakers you must not exceed the specified short-circuit<br />
ratings of the busbar trunking systems.<br />
It depends on the level of expected short-circuit current, whether<br />
a current limiting protective device is required and what shortcircuit<br />
breaking capacity the protective device must have.<br />
The table below contains an overview of the circuit breakers<br />
which are suitable for short-circuit and overload protection<br />
(400 V and 50 Hz) of the corresponding busbar system.<br />
The following applies:<br />
I’’ k ≤ I cc ≤ I cu<br />
with<br />
I’’ k = the expected short-circuit current at the site of installation<br />
I cc = rated conditional short-circuit current<br />
of the busbar trunking system<br />
I cu = rated short-circuit breaking capacity<br />
of the circuit breaker<br />
Type Rated current Circuit breaker<br />
with normal<br />
switching<br />
Rated conditional<br />
short-circuit<br />
current<br />
Circuit breaker<br />
with medium<br />
switching<br />
Rated conditional<br />
short-circuit<br />
current<br />
Circuit breaker<br />
with high<br />
switching<br />
Rated conditional<br />
short-circuit<br />
current<br />
capacity<br />
capacity<br />
capacity<br />
I n I cu I cc<br />
I cu I cc<br />
I cu I cc<br />
A<br />
kA kA<br />
kA kA<br />
kA kA<br />
BD2A(C)-160 160 3VL27 16-1... 40 20 3VL27 16-2... <strong>70</strong> 20 3VL27 16-3... 100 20<br />
BD2A(C)-250 250 3VL37 25-1... 40 40 3VL37 25-2... <strong>70</strong> 50 3VL37 25-3... 100 50<br />
BD2A(C)-400 400 3VL47 40-1... 45 45 3VL47 40-2... <strong>70</strong> 45 3VL47 40-3... 100 45<br />
BD2A(C)-630 630 3VL57 63-1DC36 45 45 3VL57 63-2DC36 <strong>70</strong> <strong>70</strong> 3VL57 63-3DC36 100 100<br />
BD2A(C)-800 800 3VL57 80-1SE36 50 50 3VL57 80-2SE36 <strong>70</strong> <strong>70</strong> 3VL57 80-3SE36 100 100<br />
BD2A(C)-1000 1000 3VL77 10-1SE36 50 50 3VL77 10-2SE36 <strong>70</strong> 60 3VL77 10-3SE36 100 60<br />
BD2C-1250 1250 3VL77 12-1SE36 50 50 3VL77 12-2SE36 <strong>70</strong> 60 3VL77 12-3SE36 100 60<br />
5<br />
The values for the conditional rated short-circuit current I cc<br />
apply to the busbar trunking systems without consideration of<br />
any tap-off units.<br />
<strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong><br />
5/81