BD2 System — 160 ... 1250 A<br />
© <strong>Siemens</strong> AG <strong>2011</strong><br />
General data<br />
Tap-off units<br />
Conductor cross-sections (geometric) 1)<br />
Designation Type L1, L2, L3 N PE Size of<br />
Up to 25 A BD2-AK1/S14 0.5 (f, st) 4 (so) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) --<br />
BD2-AK1/S18 0.5 (f, st) 16 (so, f, st) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) --<br />
BD2-AK1/A... 0.75 (so, st) 16 (so) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) --<br />
BD2-AK1/A...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 1 (so, f, st) 6 (so, st) --<br />
BD2-AK1/F... 0.75 (so, st) 16 (so) 1 (so, st) 6 (so) 1 (so, f, st) 6 (so, st) --<br />
BD2-AK1/F...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 1 (so, f, st) 6 (so, st) --<br />
Up to 63 A BD2-AK.2X/S18 0.5 (f, st) 25 (f, st) 1 (so, f, st) 16 (so, st) 1 (so, f, st) 16 (so, st) --<br />
BD2-AK.2X/S27 0.75 (f, st) 10 (so, f, st) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) --<br />
BD2-AK.2X/S33 1.5 (f, st) 25 (f, st) 2.5 (so, f, st) 16 (so, st) 2.5 (so, f, st) 16 (so, st) --<br />
BD2-AK.2M2/A... 0.75 (so, st) 25 (st) 2.5 (so, f, st) 25 (st) 2.5 (so, f, st) 25 (st) --<br />
BD2-AK.2M2/A...N 0.75 (so, st) 25 (st) 0.75 (so, f, st) 25 (st) 2.5 (so, f, st) 25 (st) --<br />
BD2-AK.2X/F... 0.75 (so, st) 25 (st) 2.5 (so, f, st) 25 (st) 2.5 (so, f, st) 25 (st) --<br />
BD2-AK.2X/GB32... 0.75 (so, st) 16 (so, st) 0.75 (so, st) 16 (so, st) Armoring --<br />
BD2-AK.2X/GB63... 0.75 (so, st) 50 (st) 0.75 (so, st) 50 (st) Armoring --<br />
Up to 125 A BD2-AK03X/FS... 2.5 (so, st) 50 (st) 2.5 (so, st) 50 (st) 2.5 (so, st) 50 (st) --<br />
BD2-AK03X/LSD40-LSD125 2.5 (so, st) 50 (st) 2.5 (so, st) 50 (st) 2.5 (so, st) 50 (st) --<br />
BD2-AK3X/GS00 16 <strong>70</strong> 16 <strong>70</strong> 10 <strong>70</strong> M8<br />
BD2-AK.3X/GSTZ(A)00 16 <strong>70</strong> 16 <strong>70</strong> 10 <strong>70</strong> M8<br />
BD2-AK.3X/GB100... 6 (so, st) <strong>70</strong> (st) 6 (so, st) <strong>70</strong> (st) Armoring --<br />
BD2-AK03X/T(S)PNR100... 6 (so, st) 50 (st) 6 (so, st) 50 (st) Armoring --<br />
Up to 250 A BD2-AK04/SNH1 6 150 6 150 6 150 M10<br />
BD2-AK04/FS... 6 150 6 150 6 150 M10<br />
BD2-AK04/LS... 6 120 (st) 6 (so, st) 150 6 150 M8<br />
Up to 400 A BD2-AK05/SNH2 10 2 × 120 10 2 × 120 10 2 × 120 M10<br />
BD2-AK05/FS... 10 2 × 120 10 2 × 120 10 2 × 120 M10<br />
BD2-AK05/LS... 10 2 × 120 10 2 × 120 10 2 × 120 M8<br />
Up to 530 A BD2-AK06/SNH3 10 2 × 240 10 2 × 240 10 2 × 240 M12<br />
BD2-AK06/LS... 10 2 × 240 10 2 × 240 10 2 × 240 M10<br />
so = solid, st = stranded, f = finely stranded with end sleeve<br />
1) Conductor cross-sections relate to Cu cables.<br />
Cross-sections and diameters for Al cables on request.<br />
Cable and wiring entries<br />
min.<br />
mm 2<br />
max.<br />
mm 2<br />
min.<br />
mm 2<br />
max.<br />
mm 2<br />
min.<br />
mm 2<br />
max.<br />
mm 2<br />
terminal screws,<br />
bolts<br />
L1, L2, L3<br />
5<br />
Type BD2-AK1/... BD2-AK.2... BD2-AK.3... BD2-AK04 BD2-AK05 BD2-AK06<br />
Cable grommets M25 1) – – KT 3 2) 2 × KT 4 2) 2 × KT 4 2)<br />
Cable glands 3) – M25, M32, M40 M25, M40, M63 – – –<br />
For cable diameter 4) mm 11 ... 16 11 ... 27 11 ... 42 14 ... 54 14 ... 68 14 ... 68<br />
Min./max. cable cross-section for NYY and<br />
NYCWY for multi-core cables<br />
• NYY... mm 2 5 × 1.5 to<br />
5 × 4<br />
•NYCWY... 5) mm 2 4 × 1.5 to<br />
4 × 2.5<br />
5 × 1.5 to<br />
5 × 16<br />
4 × 1.5 to<br />
4 × 16<br />
5 × 1.5 to<br />
5 × 25<br />
4 × 1.5 to<br />
4 × <strong>70</strong><br />
– – –<br />
5 × 1.5 to<br />
4 × 150<br />
2 × 5 × 1.5 to<br />
2 × 4 × 150<br />
Cable entry plate for singe-core cable<br />
(plates fitted, undrilled)<br />
• Max. number of cable entries – – – 10 × M40 10 × M32,<br />
5 × M40<br />
1) Strain relief in BD2-AK1/...<br />
With strain relief.<br />
3) For cable glands: Use plastic cable glands with strain relief<br />
(not included in scope of supply).<br />
4) Diameter values relate to Cu cables.<br />
Cross-sections and diameters for Al cables on request.<br />
5) Fifth conductor: concentric conductor.<br />
2 × 5 × 10 to<br />
2 × 4 × 240<br />
10 × M40<br />
5/20 <strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong>