CD-K System — 25 ... 40 A<br />
Introduction<br />
Version<br />
Type-tested low-voltage switchgear and controlgear assembly<br />
(TTA) according to<br />
• IEC/EN 60439-1<br />
• IEC/EN 60439-2<br />
Degree of protection<br />
• High degree of protection to IP54 of the standard version<br />
• Increase to IP55 with accessories<br />
Components<br />
■ Design<br />
Trunking units<br />
NSV0_00001<br />
3<br />
2<br />
1<br />
Trunking units<br />
• 3-, 4-, 5- and 3/5-conductor system<br />
• Equipment on one side:<br />
-2 or 3 tap-off plugs spaced 1 m apart<br />
-5 outgoing feeders spaced 0.5 m apart<br />
• Equipment on two sides:<br />
-2, 3 or 5 outgoing feeders spaced 1 m apart<br />
-2, 3 or 5 outgoing feeders spaced 0.5 m apart<br />
• Lengths of 2 m and 3 m<br />
• Plug-in connection<br />
• Codable tap-off points<br />
Feeder units<br />
• Entry feeder units<br />
• End feeder units<br />
Tap-off plugs<br />
• 3-pole, 10 A and 16 A, Lx (phase can be changed over<br />
optionally to L1, L2, L3 ), N and PE<br />
• 5-pole, 10 A and 16 A, L1, L2, L3, N, PE<br />
Optional equipment<br />
• End flange<br />
• Fixing bracket<br />
• Suspension hook<br />
• Suspension brackets<br />
• Cable fixture<br />
• Coding sets<br />
• Degree of protection IP55<br />
■ Benefits<br />
7 <strong>Low</strong>er planning costs through simple configuration<br />
7 Time-saving mounting through plug-in quick connector<br />
7 Tap-off points on both sides for optimized utilization of the busbar<br />
line<br />
7 Uniform current loading of the conductors through splitting of<br />
the tap-off plugs among the individual phases<br />
7 Tap-off plugs allow fast and flexible load relocation<br />
7 Accessories for increasing the degree of protection to IP55 for<br />
extreme ambient conditions<br />
1<br />
2<br />
3<br />
Locating section<br />
Connection terminal<br />
Tap-off point<br />
The trunking units are available in 2 and 3 meter lengths. They<br />
comprise a square, tin-plated metal enclosure painted graywhite.<br />
They are equipped with insulated circular conductors on one or<br />
two sides:<br />
• 2 conductors for L1 + N (PE = enclosure), one-side<br />
• 3 conductors for L1 + L2 + N (PE = enclosure), one-side<br />
• 4 conductors for L1 + L2 + L3 + N (PE = enclosure), one-side<br />
or two-side<br />
• 2 conductors for L3 + N (PE = enclosure) and<br />
4 conductors for L1 + L2 + L3 + N (PE = enclosure).<br />
Single conductor run:<br />
tap-off points at intervals<br />
of 0,5 or 1 m<br />
The tap-off points are arranged evenly on the trunking unit at a<br />
distance of 0.5 or 1 m apart.<br />
The trunking unit enclosure acts as the PE conductor. Three current<br />
intensities are available: 2 × 25 A, 30 A, 40 A and 2 × 40 A.<br />
All trunking units are equipped with finger-safe tap-off points.<br />
The tap-off points can be subsequently coded.<br />
Connection technology<br />
The trunking units, including those with feeder units and end<br />
flanges, are assembled without tools by straightforward plug-in<br />
connection. The PE path is established automatically when the<br />
enclosures are connected.<br />
An interlock mechanism with two fixings prevents a loosening of<br />
the connections between the trunking units, feeder units and<br />
flanges. Two fixings prevent the connection from becoming undone.<br />
No expansion compensation is required.<br />
NSV0_00002<br />
Two conductor runs:<br />
tap-off points at intervals<br />
of 0,5 or 1 m<br />
NSV0_00003<br />
3<br />
<strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong><br />
3/3