BD2 System — 160 ... 1250 A<br />

© <strong>Siemens</strong> AG <strong>2011</strong><br />

Introduction<br />

Distribution board feeder units<br />

For BD2 connection to a distribution board.<br />

N L1 L2 L3 PE<br />

NSV0_00129<br />

BD2.-...-VE distribution board feeder unit<br />

Center feeder units<br />

Cable entry is possible from three sides. The phase sequence<br />

can be changed on site by rotating the busbar pack.<br />

BD2.-...-ME center feeder units (PE left and PE right)<br />

NSV0_00125<br />

NSV0_00127<br />

BD2-AK1/CEE165A163<br />

Sheet steel enclosed BD2-AK2 tap-off units up to 63 A and BD2-<br />

AK3 up to 125 A with cover-integrated switch-disconnector<br />

Features:<br />

• Sheet-steel enclosure, hot-galvanized and powder coated<br />

cover, color light gray, RAL <strong>70</strong>35<br />

• The tap-off units can be mounted and removed only with their<br />

cover open.<br />

• Switch-disconnector integrated into the cover, switching capacity<br />

at 63 A AC-22B up to 400 V or at 125 A AC-21B, which<br />

ensures that the unit is not live when the cover is open.<br />

• Unintentional closing of the cover can be prevented by fitting<br />

a padlock<br />

• An anti-rotation feature prevents incorrect mounting.<br />

• Cables can be introduced from three sides; use plastic cable<br />

glands with strain relief (not in scope of supply).<br />

• Power pick-up via silver-plated lyre-shaped contacts.<br />

• If the PE conductor is used as a PEN conductor, note that the<br />

PE contact of the BD2-AK3... tap-off units have only half the<br />

cross-section and therefore cannot carry the full rated current.<br />

• The connecting cable should be supported separately if necessary.<br />

Device installation unit:<br />

For the installation of devices (e.g. miniature circuit breakers)<br />

based on DIN 43871, with 8 MW. 1 MW corresponds to a space<br />

requirement of 18 mm. Hinged covers on all tap-off units allow<br />

device operation from outside.<br />

5<br />

BD2.-...-ME center feeder units (PE rear and PE front)<br />

Tap-off units<br />

Tap-off units are available in a number of versions for different<br />

applications.<br />

BD2-AK1 molded plastic-enclosed tap-off units up to 25 A,<br />

freely assignable, with fuses, miniature circuit breakers and<br />

socket outlets<br />

Features:<br />

• Molded-plastic enclosure, color light gray, similar to RAL <strong>70</strong>35<br />

• Transparent cover for the protective devices<br />

• When mounting and disassembling the tap-off units, a load<br />

switching ability of AC-22B up to 400 V is achieved<br />

• An anti-rotation feature prevents incorrect mounting<br />

• Power pick-up through silver-plated lyre-shaped contacts<br />

• Cables can be introduced from three sides<br />

• The tap-off unit must be removed from the trunking before the<br />

unit can be opened and the cables connected<br />

• Built-in strain relief<br />

• The connecting cables should be supported separately if required<br />

NSV0_00200<br />

BD2-AK2M2/A323<br />

BD2-AK02 tap-off units up to 63 A, freely assignable,<br />

with fuses, miniature circuit breaker and socket outlets<br />

Features:<br />

• Miniature circuit breakers can be externally operated if<br />

required (device installation unit with 8 MW; 1 MW = 18 mm)<br />

NSV0_00135<br />

BD2-AK2X/CEE325S33<br />

5/8 <strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong>