BD2 System — 160 ... 1250 A<br />

© <strong>Siemens</strong> AG <strong>2011</strong><br />

Fire barrier<br />

Fire resistance rating S120<br />

• Wall thickness 150 mm ≤ M < 250 mm<br />

(distance from wall/inside corner 30 mm ≤ A < 200 mm)<br />

BD2A-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

A 30 ... 190<br />

100<br />

X*(Y*)(X*(Y*) min. =<br />

285+M+A+1<strong>70</strong>)<br />

BX*(BY*) min. =<br />

285+M/2<br />

640 (min.) 360 360<br />

– – –<br />

1250 (max.) 360 9<strong>70</strong><br />

BX*(BY*) max. =<br />

X*(Y*)-1<strong>70</strong>-A-M/2<br />

M =150 ... 250<br />

100<br />

NSV0_01031<br />

• Junction units <strong>LV</strong>, LH; 400 A<br />

X*(Y*)(X*(Y*) min. =<br />

285+M+A+<strong>70</strong>)<br />

BX*(BY*) min. =<br />

285+M/2<br />

540 (min.) 360 360<br />

– – –<br />

1250 (max.) 360 10<strong>70</strong><br />

BX*(BY*) max. =<br />

X*(Y*)-<strong>70</strong>-A-M/2<br />

• Junction units <strong>LV</strong>, LH; 1000 A<br />

X*(Y*)(X*(Y*) min. =<br />

285+M+A+130)<br />

BX*(BY*) min. =<br />

285+M/2<br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

600 (min.) 360 360<br />

– – –<br />

1250 (max.) 360 1010<br />

The dimension X* min or Y* min on the side with corner covering is<br />

460 mm.<br />

Fire resistance rating S120<br />

• Wall thickness M ≥ 250 mm<br />

(distance from wall/inside corner 30 mm ≤ A < 200 mm)<br />

BD2A-...-L... + BD2-S120-BX*(BY*)-M* 1)<br />

• Junction units LL, LR<br />

A 30 ... 190<br />

100<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+1<strong>70</strong>)<br />

BX*(BY*) min. =<br />

185+M/2<br />

640 (min.) 310 310<br />

– – –<br />

1250 (max.) 310 920<br />

BX*(BY*) max. =<br />

X*(Y*)-1<strong>70</strong>-A-M/2<br />

M 250<br />

NSV0_01032<br />

• Junction units <strong>LV</strong>, LH; 400 A<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+<strong>70</strong>)<br />

BX*(BY*) min. =<br />

185+M/2<br />

540 (min.) 310 310<br />

– – –<br />

1250 (max.) 310 1020<br />

BX*(BY*) max. =<br />

X*(Y*)-<strong>70</strong>-A-M/2<br />

5<br />

1) Replace the asterisk * according to the table.<br />

Note: With other fire barrier configurations, please contact your<br />

local <strong>Siemens</strong> sales office.<br />

• Junction units <strong>LV</strong>, LH; 1000 A<br />

X*(Y*)(X*(Y*) min. =<br />

185+M+A+130)<br />

BX*(BY*) min. =<br />

185+M/2<br />

BX*(BY*) max. =<br />

X*(Y*)-130-A-M/2<br />

600 (min.) 310 310<br />

– – –<br />

1250 (max.) 310 960<br />

The dimension X* min or Y* min on the side with corner covering is<br />

460 mm.<br />

5/98 <strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong>