BD2 System — 160 ... 1250 A<br />
Introduction<br />
BD2-AK3 tap-off units up to 125 A<br />
with fuse switch-disconnectors and fuse bases<br />
Features:<br />
• On versions with fuse switch-disconnectors or circuit breakers,<br />
the cover is interlocked with these switches and can<br />
therefore be opened only when they are switched off.<br />
• On versions with fuse bases, the isolator built into the cover<br />
does not disconnect the load. It only removes the voltage from<br />
the installed fuse bases when the cover is opened.<br />
• Terminal bolts for cables.<br />
Device installation unit:<br />
For the installation of devices (e.g. miniature circuit breakers)<br />
based on DIN 43871, with 8 MW. 1 MW corresponds to a space<br />
requirement of 18 mm. Hinged covers on all tap-off units allow<br />
device operation from outside.<br />
BD2-AK02 tap-off units up to 63 A, freely assignable,<br />
with fuses, miniature circuit breaker<br />
Features:<br />
• Miniature circuit breakers can be externally operated if required<br />
(device installation unit with 8 MW; 1 MW = 18 mm)<br />
NSV0_00131<br />
NSV0_00136<br />
BD2-AK3X/GSTZ00<br />
BD2-AK2 tap-off units up to 63 A and BD2-AK3 up to 125 A<br />
equipped to customer specifications<br />
Features:<br />
• Device installation to customer specification in compliance<br />
with the requirements for type-tested low-voltage switchgear<br />
and controlgear assemblies (TTA). Configuration, quotations<br />
and delivery through your <strong>Siemens</strong> contacts in our branches.<br />
• Device fixture on holed plates, module strip or mounting rail<br />
according to EN 60715<br />
BD2-AK02M2/A323<br />
BD2-AK03 tap-off units up to 125 A<br />
with circuit breakers, fuse switch-disconnectors, fuse bases,<br />
miniature circuit breakers and fuse switches<br />
Features:<br />
• On versions with fuse switch-disconnectors or circuit breakers,<br />
the cover is interlocked with these switches and can<br />
therefore be opened only when they are switched off.<br />
• Terminal bolts for cables<br />
• Miniature circuit breakers can be externally operated if<br />
required (device installation unit with 8 MW; 1 MW = 18 mm)<br />
NSV0_00138<br />
NSV0_01465<br />
BD2-AK2...<br />
BD2-AK02 (AK03) sheet-steel enclosed tap-off units<br />
without cover-integrated switch-disconnector<br />
Features:<br />
• Sheet-steel enclosure, hot-galvanized and powder coated<br />
cover, color light gray, RAL <strong>70</strong>35<br />
• The tap-off units can be mounted and removed with their<br />
cover open and closed.<br />
• With the cover open the voltage is still applied to the installed<br />
devices (test facility). Degree of protection IP20 (finger-safe) is<br />
assured.<br />
• Do not mount or remove tap-off units under load.<br />
• An anti-rotation feature prevents incorrect mounting.<br />
• Cables can be infed from 3 directions, use plastic screwed<br />
cable glands with strain relief (not included in the scope of<br />
supply).<br />
• Power pick-up via silver-plated lyre-shaped contacts.<br />
• If the PE conductor is used as a PEN conductor, note that the<br />
PE contact of the BD2-AK03 tap-off units have only half the<br />
cross-section and therefore cannot carry the full rated current.<br />
• The connecting cable should be supported separately if<br />
necessary.<br />
BD2-AK03X/L...<br />
5<br />
<strong>Siemens</strong> <strong>LV</strong> <strong>70</strong> · 04/<strong>2011</strong><br />