<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong>IO Servers Configuration5.10.2.3 Analog Input Value Range (<strong>eWON</strong>4002)The Analog Inputs (AI1 to AI6) come from a 12 bits ADC. Then, the values read on a AI# tag go from 0 to 4095.5.10.2.3.1 Configurable analog input AI1 to AI4• In 0-10V modeAI#Volt0 04095 10If you need to read the Tag value converted in Volt, you can set a factor of 0.0024420 = 10/4095 with an offset of 0.Figure 92: Tag’s configuration: reading the tag value in Volt• In 0-20 mA modeThe shunt resistor for measuring current is a 220 Ohm.AI#mA0 01802 20If you need to read the Tag value converted in mA, you can set a factor of 0.011099 = 20/1802 with an offset of 0.Figure 93: Tag’s configuration: reading the tag value in mARG-001-0-EN ver 1.5 <strong>eWON</strong>® - 20/03/2009 - ©ACT'L sa Page 121