<strong>General</strong> <strong>Reference</strong> <strong>Guide</strong>Monitoring Web Interface6.7.4.2 Activate Energy debug modeFigure 136: Activate Energy debug6.7.4.3 Activate Serial debug modeYou can activate the debug mode on every serial port of the <strong>eWON</strong> (COM port(s) and Modem).Syntax is SerDebX:Y X is the Serial port number and Y is the debug mode.<strong>eWON</strong> type Serial port number ( X )<strong>eWON</strong>4002<strong>eWON</strong> MPIOther <strong>eWON</strong>s1 : Serial port 12 : Modem3 : Serial port 24 : Serial port 31 : Modem1 : Serial port 12 : ModemTable 133: Serial Debug : Serial port availableDebug mode value (Y)Description0 No debug1 Hex values Tx & Rx2 Hex and Ascii values Tx & Rx3Hex and Ascii values Tx & Rxbut Rx timeouts are not logged (clearer in log)(usefull for Modem debugging)Table 134: Serial Debug : mode valuesTo enable the Serial debug mode on Serial port 1, you need to send by FTP a “config.txt” file containing only:::SystemSerDeb1:1Or you can use a little Script Basic:Setsys SYS,”load”Setsys SYS,”SerDeb1”,1Setsys SYS,”save”cfgsave : REM to debug also after rebootRG-001-0-EN ver 1.5 <strong>eWON</strong>® - 20/03/2009 - ©ACT'L sa Page 162